24 160-54-OI-GB0<br />

9.1.1 TREND SETUP SCREEN<br />

The Slot Nos (see Section 9.1.2) and Select buttons are<br />

used to enter the slot numbers and the minimum and<br />

maximum Y-Axis values of each parameter to be<br />

trended.<br />

The slot number can be obtained from the Common<br />

Slots Screen or Master Slot Number List. Setting this<br />

slot number to zero will disable trending for that<br />

particular Data Point.<br />

There are 20 Y-Axis divisions between the minimum<br />

and maximum values. If a MIN-MAX span is selected<br />

that is not evenly divided by 20, the program will<br />

automatically select the next higher MAX value that<br />

makes the span divisible by 20. The minimum value<br />

must always be set to a value less than the maximum<br />

value and the minimum value should be set to zero (0)<br />

for digital parameters with the maximum value set to one<br />

(1).