34 160-54-OI-GB0<br />

LCSSS - STOP CONTACTS OPEN<br />

See 'LCSSS SHUTDOWN – REQUESTING FAULT<br />

DATA...'.<br />

If the microprocessor board in the control panel does not<br />

receive the cause of a starter initiated shutdown within<br />

20 seconds of the shutdown, it is assumed it is not<br />

available and that message is replaced with this<br />

message. The unit can be started when the Motor<br />

Controller LCSSS Stop Contacts close.<br />

A missing interlock jumper between the<br />

LCSSS logic/trigger board J1-1 and J1-12will<br />

also produce this message.<br />

LCSSS - POWER FAULT<br />

The LCSSS logic/trigger board has detected that the<br />

compressor motor current in one or more phases has<br />

decreased to 25% of<br />

the motor FLA. The unit will automatically restart upon<br />

completion of 'SYSTEM COASTDOWN'.<br />

LCSSS - LOW PHASE (X) TEMPERATURE SENSOR<br />

The LCSSS logic/trigger board has detected that the<br />

temperature of the starter phase A, B or C (designated<br />

as X in the message) Silicon Controlled Rectifier (SCR)<br />

module has decreased to < 2.8 °C (37 °F). This would<br />

generally indicate a disconnected or defective sensor.<br />

If all three SCR modules are indicating a temperature of<br />