34 160-54-OI-GB0<br />
LCSSS - STOP CONTACTS OPEN<br />
See 'LCSSS SHUTDOWN – REQUESTING FAULT<br />
DATA...'.<br />
If the microprocessor board in the control panel does not<br />
receive the cause of a starter initiated shutdown within<br />
20 seconds of the shutdown, it is assumed it is not<br />
available and that message is replaced with this<br />
message. The unit can be started when the Motor<br />
Controller LCSSS Stop Contacts close.<br />
A missing interlock jumper between the<br />
LCSSS logic/trigger board J1-1 and J1-12will<br />
also produce this message.<br />
LCSSS - POWER FAULT<br />
The LCSSS logic/trigger board has detected that the<br />
compressor motor current in one or more phases has<br />
decreased to 25% of<br />
the motor FLA. The unit will automatically restart upon<br />
completion of 'SYSTEM COASTDOWN'.<br />
LCSSS - LOW PHASE (X) TEMPERATURE SENSOR<br />
The LCSSS logic/trigger board has detected that the<br />
temperature of the starter phase A, B or C (designated<br />
as X in the message) Silicon Controlled Rectifier (SCR)<br />
module has decreased to < 2.8 °C (37 °F). This would<br />
generally indicate a disconnected or defective sensor.<br />
If all three SCR modules are indicating a temperature of<br />