8 SETPOINTS SCREEN<br />
The 'SETPOINTS SCREEN' displays the current<br />
operating leaving chilled liquid temperature setpoint and<br />
remote range, low leaving chilled liquid temperature<br />
cycling shutdown and restart values and there offset<br />
and the current limit setpoint.<br />
The local leaving chilled liquid temperature 'SETPOINT'<br />
and 'RANGE', low leaving chilled liquid temperature<br />
cycling 'SHUTDOWN' and 'RESTART' values, 'LOCAL<br />
MOTOR CURRENT LIMIT' and 'PULLDOWN DEMAND<br />
LIMIT' and 'TIME' and 'REMOTE ANALOGUE INPUT<br />
RANGE' should be programmed on this screen:<br />
Setpoint<br />
Defines the leaving chilled liquid temperature that is to<br />
be maintained by the unit. The 'SETPOINT' can be<br />
programmed between 3.3°C (38°F) and 21.1°C (70°F)<br />
for water cooling applications or -12.2°C (10°F) and<br />
21.1°C (70°F) for brine/glycol applications.<br />
When Smart Freeze has been enabled by a<br />
qualified Service Technician, the<br />
programmable 'SETPOINT' is 2.2°C (36°F) to<br />
21.1°C (70°F) for water cooling applications.<br />
Range<br />
160-54-OI-GB0 15<br />
The programmed 'SETPOINT' can be reset (offset)<br />
upwards by an analogue signal: (0-20 mA, 4-20 mA,<br />
0-10 Vdc or 2-10 Vdc) in the analogue remote mode, or<br />
PWM signal in digital remote mode. The offset<br />
('RANGE') may be programmed to 5.6°C (10°F) or<br />
11.1°C (20°F) (11.1°C is the default 'RANGE').<br />
For example, if the 'SETPOINT' is programmed for 7°C<br />
and the programmed 'RANGE' is 5.6°C, then the remote<br />
device can set the leaving chilled liquid temperature<br />
setpoint over the range 7°C to 12.6°C.<br />
Additionally, a remote GPIC device (in ISN<br />
remote mode) can define the setpoint through<br />
a serial data stream.