Cycling Offset - Shutdown<br />
Defines the leaving chilled liquid temperature at which<br />
the unit will shutdown on a 'LEAVING CHILLED <strong>LIQUID</strong><br />
- LOW TEMPERATURE'. The 'OFFSET' (below<br />
'SETPOINT') can be programmed between 0.56°C<br />
(1°F) and 35.6°C (64°F) to a minimum cut-out of 2.2°C<br />
(36°F) for water cooling applications (1.1°C (34°F) with<br />
Smart Freeze enabled) or -14.4°C (6°F) for brine/glycol<br />
applications.<br />
When the programmed leaving chilled liquid<br />
temperature 'SETPOINT' is changed, the shutdown is<br />
fixed at of 2.2°C (36°F) for water cooling applications<br />
(1.1°C (34°F) with Smart Freeze enabled) or -14.4°C<br />
(6°F) for brine/glycol applications for the next ten<br />
minutes.<br />
The shutdown will then revert to the 'SETPOINT' plus<br />
the 'OFFSET' after ten minutes has elapsed.<br />
Cycling Offset - Restart<br />
160-54-OI-GB0 7<br />
Defines the leaving chilled liquid temperature at which<br />
the unit will restart after a 'LEAVING CHILLED <strong>LIQUID</strong> -<br />
LOW TEMPERATURE ' shutdown. The 'OFFSET'<br />
(above 'SETPOINT') can be programmed between 0°C<br />
(0°F) and 21.1°C (70°F) to a maximum restart of 26.7°C<br />
(80°F). This 'OFFSET' can be used to reduce unit<br />
cycling by delaying the restart until the cooling load has<br />
increased dramatically.<br />
Refrigerant - Service Technicians<br />
Sensitivity - Service Technicians<br />
Brine Low Evaporator Cutout - Service Technicians<br />
Smart Freeze - Service Technicians