Terminal Function / Notes Data Suggested circuit<br />
15/16 Terminals for tachogenerator<br />
(speed controller option)<br />
15 Connection of the positive voltage of<br />
the tachogenrator<br />
The polarity at the terminals must remain<br />
the same in the case of reversing the motor<br />
DIP switch at the power supply board:<br />
frequency- Speedcontrolled<br />
controlled<br />
S 3 - 1 ON (OFF) ON<br />
S 3 - 2 ON OFF<br />
S 3 - 6 OFF ON<br />
highest control point<br />
10-40V 30-100V<br />
S 3 - 7 ON OFF<br />
Only terminal 2 can be used as input for a<br />
speed setpoint.<br />
a) DC-tachogenerator one direction<br />
b) DC-tachogenerator both directions<br />
c) AC-tachogenerator with bridge-rectifier<br />
for both directions<br />
17/18 Multifunction relay<br />
Closing of the floating contact with<br />
a) programmed at "Current" I > ISet<br />
b) programmed at "<strong>Frequency</strong>" f > fSet<br />
19/20 <strong>Frequency</strong>-signalling relay<br />
Closing of the floating contact with<br />
f > fSet<br />
21/22 Fault-signalling relay<br />
Floating contact open:<br />
- Fault has occured<br />
- The inverter is disconnected from the mains<br />
Contact is shown in no-voltage<br />
condition. When the inverter is<br />
ready for operation, the contact<br />
is closed.<br />