OPERATING INSTRUCTIONS NORDAC Frequency Inverters
OPERATING INSTRUCTIONS NORDAC Frequency Inverters
OPERATING INSTRUCTIONS NORDAC Frequency Inverters
Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
10.0 Mains filter<br />
Normal version contains:<br />
- Line choke | to protect the inverter<br />
- Capacitors |---> against normal mains<br />
- Varistors | voltage peaks<br />
Special cases:<br />
- Installation of a standard mains filter ---> protects against high-frequency voltage peaks<br />
(data on request) (e.g. in the case of power-factor correction systems, welding equipment etc.)<br />
10.1 Radio interference suppression<br />
RFI suppression is possible if required.<br />
Reducing the emitted interference to the value of limit value class B in accordance with VDE 0871:<br />
- with mains-circuit coupling ---> by use of standard RFI suppression filters<br />
- with emitted interference ---> by use of a screened cable or<br />
of the motor supply line lay in earthed heavy-gauge steel conduit<br />
a) Arrange earth connection (PE) a)<br />
- ensure very low resistance<br />
- arrange connection/transition with<br />
large cross-section<br />
Screening<br />
- bring as close as possible to the<br />
inverter and the motor (< 0,2 m)<br />
- do not interrupt<br />
- connect on both sides to earth (PE)<br />
If (a) is not sufficient to suppress<br />
interference --> try b)<br />
b) As a), but in more advanced form, with b)<br />
line compensation choke or standard output<br />
filter with higher damping<br />
(chokes and filters available on request<br />
at extra charge)<br />
29