4.2 Control section<br />

Connection for the control lines - 22-pole control terminal strip on the mains power supply board,<br />

subdivided into three blocks<br />

Maximum connection cross sectional - 1,5 mm 2<br />

area<br />

4.2.1 Control terminal strip Setpoint - shield lines.<br />

(short lines twisted at least)<br />

Reference potential for the setpoints (GND)<br />

Setpoint - 10 V / 0 / + 10 V DC<br />

Setpoint - 10 V / 0 / + 10 V DC<br />

Setpoint 0 (4) ... 20 mA<br />

+ 10 V reference voltage<br />

Reversing<br />

Electronic release<br />

Fault acknowledgement<br />

PTC thermistor/tempearture sensor<br />

PTC thermistor/temperature sensor<br />

Parameter switchover input 1<br />

Parameter switchover input 2<br />

Digital frequency output<br />

Reference potential for the control inputs<br />

(GND)<br />

Tachogenerator + *)<br />

Tachogenerator - *)<br />

max.load rating 240 V ~ / 60 V = ; 0,8 A Multifunction relay<br />

max.load rating 240 V ~ / 60 V = ; 0,8 A <strong>Frequency</strong> signalling relay<br />

max.load rating 240 V ~ / 60 V = ; 0,8 A Fault signalling relay<br />

*) Option<br />