which closes in case of my internal fault(s) in the shunt capacitor bank.<br />
II. From each SP<br />
1. 110V dc low..<br />
2. 240V ac fail<br />
3. Catenary-1 fail<br />
4. Catenary-2 fail<br />
5. Catenary-3 fail<br />
6. Catebary-4 fail<br />
7. AT-1 Alarm<br />
8. AT-1 Fault<br />
9. AT-2 Alarm<br />
10. T-2 Fault<br />
11. At-3 Alarm<br />
<strong>12</strong>. AT-3 Fault<br />
13. AT-4 Alarm<br />
14. AT-4 Fault<br />
15. CB.1 ―Locked out‖ due to low gas/air pressure.<br />
16. CB.2 ―Locked out‖ due to low gas/air pressure.<br />
For details of AT-1 to 4 Alarms and At-1 to 4 Faults, explanation given in clause No.<br />
5.5.1.I.b (iv) may be seen.<br />
III. From each SSP<br />
1. 110V dc low<br />
2. 240V ac fail<br />
3. Catenary-1 fail (wherever required)<br />
4. Catenary-2 fail (wherever required)<br />
5. AT-1 Alarm<br />
6. AT-1 Fault<br />
7. AT-2 Alarm<br />
8. AT-2 Fault<br />
For details of AT-1 to 2 Alarms and At-1 to 2 Faults, explanation given in clause No.<br />
5.5.1.I.b (iv) may be soon.<br />
IV. From each ATP<br />
1. AT-1 Alarm<br />
2. AT-1 Fault<br />
3. AT-2 Alarm<br />
4. AT-2 Fault<br />
5. 240V ac fail<br />
6. 110V dc low<br />
For details of AT-1 to 2 Alarms and At-1 to 2 Faults, explanation given in clause No.<br />
5.5.1.I.b (iv) may be seen.<br />
5.5.2 The protective relays viz. OCR, DPR and delta-I relay reset themselves<br />
immediately after operation.<br />
- 10 -<br />
5.5.3 Amongst the above tele-signals, the monitoring of ―dc low‖<br />
Indications shall be through solid-state comparator circuits, while that of ―a.c. fail‖ and