6.1.6 Data-logging printers<br />
- 23 -<br />
6.1.6.1 Two alphanumeric dot-matrix printers with a printing speed or 189<br />
characters per second shall be provided. The printer shall have 132 columns with facility<br />
for friction roller and tractor paper feed. It shall be robust and noiseless.<br />
6.16.2 Data-logging<br />
a) Alarm/Event logging<br />
Logging shall be done of the following:<br />
All events such as signals and alarms, commanded and uncommanded<br />
changes and limit violations of telemetered parameters shall be printed automatically by<br />
the data-logger with date (year, month and day) and time of occurance (hours, minutes,<br />
seconds and milli-seconds) stamp.<br />
b) Diagnostics<br />
The system shall provide diagnostic checks for faults in<br />
(i) The SCADA equipment at the RCC,<br />
(ii) In the communication lines and<br />
(iii) at the controlled stations<br />
These faults shall be printed out with details such as name of controlled<br />
station, card number with date and time stamp.<br />
c) On-demand facility<br />
The facility shall be provided for the operator to obtain reports on-demand<br />
through the keyboard. Such reports may include current status of bistate devices, signals<br />
and alarms at the remote stations, communication failures, telemetry printout and other<br />
information required.<br />
d) Periodic printouts<br />
The dataloggar shall give periodic printouts, whenever required by the<br />
operator, as under:<br />
(i) 15/30 minutes printout giving average values of all the analogue<br />
parameters at TSSs and SPs during the last 15/30 minute period.