- 56 -<br />

ANUEXURE= 3<br />

SALIENT FEAATURES OF 25KV CURRENT AND POTENTIAL<br />

TRANS<strong>FOR</strong>MERS<br />

A) Current Transformers<br />

i) Type Low reactance, single phase, oil filled,<br />

ii) a) National system voltage 27 kV<br />

b) highest equipment voltage 52 kV<br />

iii) Frequency 50 Hz<br />

iv) Rated primary current 1000/500 A<br />

v) Rated secondary current 5 A.<br />

vi) Rated transformation ratio 1000-500/5<br />

vii) Rated burden 60 VA<br />

viii)Accuracy class 5P<br />

self-cooled scaled outdoor types.