- 25 -<br />

6.2.3.2 The ac supply will have voltage surges and spikes due to the switching<br />

ON/OFF of the traction loads. Hence the power supply units shall include suitable surge<br />

suppressors to effectively suppress the voltage surges, spikes and the electrical noise in<br />

the incoming a.c. supply.<br />

6.2.4 Parameters to telemetered/computed (measurands)<br />

6.2.4.1 The RTUs shall be designed to telemetere two feeder currents and two OHE<br />

voltages from each TSS, and two OHE voltages from each SP. The arrangement for<br />

telemetry shall be as under:<br />

(a) From TSS<br />

i) Feeder currents: Two current transducers shall be provided, one<br />

each for either side of the TSS, taking reference from the two feeder CTs of that side<br />

through a summation CT. The summation CTs shall form part of the RTU.<br />

ii) Feeder voltages: Two voltage transducers shall be provided, one<br />

each for either side of the TSS, taking reference from the two OHE PTs of that side<br />

through a suitable change-over device. In the event of supply failure in any of the PTs,<br />

The change-over device shall automatically connect the live PT to the transducer. The<br />

change-over devices shall form part of the RTU.<br />

b) From SP<br />

Voltage of the OHE on either side: Two voltage transducers shall be<br />

provided, taking reference either from the UP or DOWN line PT through a suitable<br />

change-over device which shall form part of the RTU.<br />

6.2.5 Transducers<br />

6.2.5.1 Transducers provided at the controlled stations (TTS and SP) shall be<br />

Auxiliary-powered and of quick response type with a response time not greater than 1<br />

second. They shall have linear characteristic over the entire range with accuracy of +/-<br />

0.5%. Transducers shall give an output proportional to the input from current<br />

transformers and potential transformers at the TSS and at the SP as the case may be.<br />

6.2.5.2 The salient features of CTs and PTs provided at the TTS. SSPs, SPs are at<br />

Annuxure-3.