2.3 Atmospheric Conditions<br />

Maximum average ambient temperature<br />

Minimum ambient temperature<br />

Relative humidity<br />

… 45 deg C<br />

… 0 deg C<br />

... 100 %<br />

The locations at which the equipment is to function shall be subjected to dust<br />

storms in summer, and to heavy rains and lightning during monsoon.<br />

2.4 The SCADA system is intended for use at altitude not exceeding 1000 metres.<br />

2.5 Voltage and frequency<br />

2.5.1 At RCC : 415 V, 3 phase 50 Hz supply from the State Electricity Board shall<br />

be made available by the Railways. The voltage may vary between +10% and -15%, while<br />

the frequency between +3% and -3% of the nominal values. The master station equipment<br />

shall be suitable for satisfactory operation throughout these variations.<br />

2.5.2.1 240V, single phase 50 Hz a.c.supply from the auxiliary transformers provided<br />

at controlled stations shall be made available by the Railways. Due to variation in the<br />

catenary voltage(25kV). The single phase voltage may vary between 180 V and 265 V.<br />

The frequency may vary between +3% and -3% of the nominal value. The RTU equipment<br />

shall normally operate off this a.c. supply and be suitable for satisfactory operation<br />

throughout variations in voltage and frequency.<br />

2.5.2.2 Operation (open/close) of circuit breakers, interruptors and other<br />

equipments is carried out at 110 V d.c. For this purpose necessary battery charger shall<br />

be provided by the railways.<br />

2.5.2.3 In case of failure of a.c. supply at the controlled station, the RTU shall<br />

automatically operate off the 110 V d.c. supply. The d.c. voltage may vary between +l0%<br />

and -15% of the nominal value. The RTU shall be suitable for satisfactory operation<br />

throughout this variation.<br />

3.0 Governing specifications<br />

3.1 The SCADA equipment and component thereof shall, unless otherwise<br />

specified, conform generally to the latest editions of the Bureau of Indian Standards<br />

specification mentioned below:<br />

IS:590 Fixed paper dielectric capacitors.<br />

IS:1554 PVC (Heavy duty) insulated electric cables.<br />

IS:1652 Stationary cells and batteries, lead-acid type with plants positive plates.<br />

IS:1765 Direct current Potentiometers.