2.3 Atmospheric Conditions<br />
Maximum average ambient temperature<br />
Minimum ambient temperature<br />
Relative humidity<br />
… 45 deg C<br />
… 0 deg C<br />
... 100 %<br />
The locations at which the equipment is to function shall be subjected to dust<br />
storms in summer, and to heavy rains and lightning during monsoon.<br />
2.4 The SCADA system is intended for use at altitude not exceeding 1000 metres.<br />
2.5 Voltage and frequency<br />
2.5.1 At RCC : 415 V, 3 phase 50 Hz supply from the State Electricity Board shall<br />
be made available by the Railways. The voltage may vary between +10% and -15%, while<br />
the frequency between +3% and -3% of the nominal values. The master station equipment<br />
shall be suitable for satisfactory operation throughout these variations.<br />
2.5.2.1 240V, single phase 50 Hz a.c.supply from the auxiliary transformers provided<br />
at controlled stations shall be made available by the Railways. Due to variation in the<br />
catenary voltage(25kV). The single phase voltage may vary between 180 V and 265 V.<br />
The frequency may vary between +3% and -3% of the nominal value. The RTU equipment<br />
shall normally operate off this a.c. supply and be suitable for satisfactory operation<br />
throughout variations in voltage and frequency.<br />
2.5.2.2 Operation (open/close) of circuit breakers, interruptors and other<br />
equipments is carried out at 110 V d.c. For this purpose necessary battery charger shall<br />
be provided by the railways.<br />
2.5.2.3 In case of failure of a.c. supply at the controlled station, the RTU shall<br />
automatically operate off the 110 V d.c. supply. The d.c. voltage may vary between +l0%<br />
and -15% of the nominal value. The RTU shall be suitable for satisfactory operation<br />
throughout this variation.<br />
3.0 Governing specifications<br />
3.1 The SCADA equipment and component thereof shall, unless otherwise<br />
specified, conform generally to the latest editions of the Bureau of Indian Standards<br />
specification mentioned below:<br />
IS:590 Fixed paper dielectric capacitors.<br />
IS:1554 PVC (Heavy duty) insulated electric cables.<br />
IS:1652 Stationary cells and batteries, lead-acid type with plants positive plates.<br />
IS:1765 Direct current Potentiometers.