6.9.13 All the equipments viz. computer, VDUs, key-boards, date logging<br />
printers etc. and components used in the SCADA system shall be of industrial grade. A<br />
certificate to this effect shall be furnished by the tederer.<br />
6.9.14 The micro-computers used, If any, shall be IBM compatible.<br />
6.9.15 The mimic-driver cabinets and the layout of the traction power supply<br />
diagrams on the MDB shall be so designed as to convert any SP to TSS, if required, by<br />
simply adding the required modules in the mimic driver and making minimum changes in<br />
the MDB.<br />
6.9.16 Construction of MDB<br />
(i) The MDB shall normally be not more than 3.5 m in length for 30<br />
controlled stations, 0.75 m in height and 0.2 m in width, and shall be desk-top/pedestal<br />
mounted close to the operator.<br />
(ii) The MDB shall be made of steel of thickness of 1.6 mm, reinforced<br />
wherever necessary. To prevent corrosion the steel work shall be properly treated and<br />
then given a primary coat of zinc chromate, both on the interior and exterior surfaces<br />
followed by two coats of finishing enamel paint. The inner side shall be finished with<br />
stoved enamel white paint. The external surface shall be finished with stoved enamel<br />
paint of opaline green shade number 275 as per IS:5 or any other colour decided by the<br />
railways, evenly sprayed to present a smooth and pleasing appearance.<br />
(iii) Mimic display of catenary shall be by means of LEDs and metal strips. The<br />
tederer may however offer any other state-of-the-art technique for consideration as an<br />
alternative offer.<br />
(iv) Each circuit breaker & interruptor shall be depicted with the help of a 3<br />
legged LED on the MDB. The LED shall emit red/green colour to indicate<br />
CLOSE/OPEN status respectively. The complementary fault shall be indicated by yellow<br />
colour or dark state of the LED.<br />
(v) Whenever any of the sub-sectors of OHE gets de-energised, the<br />
corresponding portion shall be lit up and start flashing until acknowledged by the<br />
operator.<br />
(vi) The scheme of connections, identification numbers for circuit breakers,<br />
interruptors and motor operated isolators, if any, and other indications on the MDB shall