6.9.13 All the equipments viz. computer, VDUs, key-boards, date logging<br />

printers etc. and components used in the SCADA system shall be of industrial grade. A<br />

certificate to this effect shall be furnished by the tederer.<br />

6.9.14 The micro-computers used, If any, shall be IBM compatible.<br />

6.9.15 The mimic-driver cabinets and the layout of the traction power supply<br />

diagrams on the MDB shall be so designed as to convert any SP to TSS, if required, by<br />

simply adding the required modules in the mimic driver and making minimum changes in<br />

the MDB.<br />

6.9.16 Construction of MDB<br />

(i) The MDB shall normally be not more than 3.5 m in length for 30<br />

controlled stations, 0.75 m in height and 0.2 m in width, and shall be desk-top/pedestal<br />

mounted close to the operator.<br />

(ii) The MDB shall be made of steel of thickness of 1.6 mm, reinforced<br />

wherever necessary. To prevent corrosion the steel work shall be properly treated and<br />

then given a primary coat of zinc chromate, both on the interior and exterior surfaces<br />

followed by two coats of finishing enamel paint. The inner side shall be finished with<br />

stoved enamel white paint. The external surface shall be finished with stoved enamel<br />

paint of opaline green shade number 275 as per IS:5 or any other colour decided by the<br />

railways, evenly sprayed to present a smooth and pleasing appearance.<br />

(iii) Mimic display of catenary shall be by means of LEDs and metal strips. The<br />

tederer may however offer any other state-of-the-art technique for consideration as an<br />

alternative offer.<br />

(iv) Each circuit breaker & interruptor shall be depicted with the help of a 3<br />

legged LED on the MDB. The LED shall emit red/green colour to indicate<br />

CLOSE/OPEN status respectively. The complementary fault shall be indicated by yellow<br />

colour or dark state of the LED.<br />

(v) Whenever any of the sub-sectors of OHE gets de-energised, the<br />

corresponding portion shall be lit up and start flashing until acknowledged by the<br />

operator.<br />

(vi) The scheme of connections, identification numbers for circuit breakers,<br />

interruptors and motor operated isolators, if any, and other indications on the MDB shall