- 11 -<br />
―PT fuse fail‖ indication through rectifier and no-volt relays, and that of ―catenary<br />
supply‖ indications through rectifier and solid-state comparator circuits. Monitoring of<br />
the balance indications shall be through 110V dc interposing relays. The rectifier,<br />
comparator circuits, no-volt relays and interposing relays shall form part of the RTUs.<br />
5.6 Tap-changer control of traction power transformers<br />
5.6.1 The traction power transformer at s TSS may be provided with motor operated<br />
off-circuit tap changer with 110V dc control circuit. For remote control of the tapchanger<br />
from the RCC, progression/regression telecommand shall be provided. The tap<br />
position shall be telesignalled to the RCC in confirmation of the telecommand.<br />
5.6.2 The tap changer switch has six tap positions. For each tap position one <strong>NO</strong><br />
type contact is provided. At any tap position, only the corresponding <strong>NO</strong> contact will<br />
remain closed and the remaining contacts will remain open.<br />
5.6.3 Each telecommand for the tap changer shall include progression/regression<br />
telecommand and the back telesignal from the TSS of the tap position.<br />
5.7 The terminal required for interfacing the controlled station with RTU at TSS<br />
shall be provided by the railways in the control and relay panel at TSS. The terminal at<br />
SP/SSP/ATP shall be provided on a terminal board mounted on the wall inside the<br />
masonry building at SP/SSP/ATP. The supply of cable and wiring between the control<br />
and relay panel/terminal board and RTU shall be done by the successful tendered. The<br />
cable shall conform to IS:1554.<br />
5.8 Underground trunk cable<br />
5.8.1 Underground telecommunication trunk cable is provided by the railway<br />
alongside the railway track. Three part of conductors (one pair for ―Send‖, one pair for<br />
―Receive‖ and third pair as spare) from this cable shall be made available for remote<br />
control purposes.<br />
5.8.2 The cable shall conform to railways specification No.TC-14/75. The salient<br />
technical particulars of the star quads Of the cable circuits made available for remote<br />
control operation are as under:<br />
(a) Dia of copper conductor 0.9mm<br />
(b) Type of insulation Paper<br />
(c) Nominal loop resistance at 55.2 ohms/km<br />
20 degree c.<br />
(d) Resistance unbalance between Not more than 1%<br />
Two conductors of a pair of nominal loop.<br />
(e) Nominal mutual capacitance of 0.041 microfarad/km.<br />
The pairs of paper insulated<br />
VF quads<br />
(f) Capacitance unbalance after<br />
Balancing of full loading<br />
section of 1.83km.<br />
(i) Between pairs (same quad) Less than 40pF