Specification No. : <strong>ETI</strong>/<strong>PSI</strong>/<strong>144</strong> (<strong>12</strong>/<strong>91</strong>)<br />

SUPERVISORY CONTROL AND DATA ACQUISITION (SCADA) SYSTEM <strong>FOR</strong><br />

2x25 kV A.T. TRACTION POWER SUPPLY<br />

1.0 Scope<br />

1.1 This specification applies to the design, manufacture, supply, erection,<br />

testing and commissioning of SCADA system to enable the Traction Power<br />

Controller(TPC) or operator, to control from a central place called Remote Control Centre<br />

(RCC), the switching operations of the equipments at traction sub-stations and switching<br />

stations (hereinafter called "controlled stations"), to monitor the status of the equipments<br />

and to collect and store information and data relating to the overall traction power supply<br />

to the 2X25 kV overhead traction lines.<br />

1.2 The SCADA equipment shall be based on the state-of-the-art technology.<br />

The equipment at RCC, here after called as master station equipment, shall include dual<br />

main mini-computer(s) system with sufficient semi-conductor RAM main memory, high<br />

speed computer to computer communication link, system consoles, man-machine<br />

interfaces through color VDUs and key-boards, front-end processors, modems, data<br />

logging printers, watch dogs, floppy disks and hard disks along with their drives, switchover<br />

unit for switching over from main to standby computer or vice-versa, mimic driver<br />

and mimic diagram board (MDB), UPSs with battery, console desks and surge arresters.<br />

1.2.1 As an alternative to the master station built around minicomputers, tenderer<br />

shall also quote for a master station built around dual main micro-computers.<br />

1.3 The SCADA equipment at controlled station, hereafter called as Remote<br />

Terminal Unit (RTU), shall be micro-processor based and shall be compatib1e with the<br />

master station equipment• It shall be complete in all respects including central processing<br />

unit with watch dog, digital input/output modules, alarm input modules, analogue input<br />

modules, transducers, memory, interposing relays, summation current transformers, power<br />

supply units, surge arresters and modem.<br />

1.4 The SCADA equipment at RCC and at controlled stations shall be complete<br />

with all units, parts and accessories necessary for their efficient operation and all such<br />

units, parts and accessories shall be deemed to be within the scope of this specification<br />

whether specifically mentioned or not.<br />

2.0 Service conditions<br />

2.1 The SCADA equipment may be installed any where in India. The<br />

equipment at RCC shall be installed indoors. Air-conditioning may be provided, if<br />

convenient, or else filtered air will be blown through to cool the equipments.<br />

2.2 The SCADA equipment at controlled stations shall be installed inside track<br />

side cubicles and subjected to vibrations on account of running trains on the near-by<br />

railway tracks. These cubicles will not be air-conditioned and are liable to exposure to<br />

polluted atmosphere.