1.0 Scope<br />
1.1 This specification applies to the design, manufacture, supply, erection,<br />
testing and commissioning of SCADA system to enable the Traction Power<br />
Controller(TPC) or operator, to control from a central place called Remote Control Centre<br />
(RCC), the switching operations of the equipments at traction sub-stations and switching<br />
stations (hereinafter called "controlled stations"), to monitor the status of the equipments<br />
and to collect and store information and data relating to the overall traction power supply<br />
to the 2X25 kV overhead traction lines.<br />
1.2 The SCADA equipment shall be based on the state-of-the-art technology.<br />
The equipment at RCC, here after called as master station equipment, shall include dual<br />
main mini-computer(s) system with sufficient semi-conductor RAM main memory, high<br />
speed computer to computer communication link, system consoles, man-machine<br />
interfaces through color VDUs and key-boards, front-end processors, modems, data<br />
logging printers, watch dogs, floppy disks and hard disks along with their drives, switchover<br />
unit for switching over from main to standby computer or vice-versa, mimic driver<br />
and mimic diagram board (MDB), UPSs with battery, console desks and surge arresters.<br />
1.2.1 As an alternative to the master station built around minicomputers, tenderer<br />
shall also quote for a master station built around dual main micro-computers.<br />
1.3 The SCADA equipment at controlled station, hereafter called as Remote<br />
Terminal Unit (RTU), shall be micro-processor based and shall be compatib1e with the<br />
master station equipment• It shall be complete in all respects including central processing<br />
unit with watch dog, digital input/output modules, alarm input modules, analogue input<br />
modules, transducers, memory, interposing relays, summation current transformers, power<br />
supply units, surge arresters and modem.<br />
1.4 The SCADA equipment at RCC and at controlled stations shall be complete<br />
with all units, parts and accessories necessary for their efficient operation and all such<br />
units, parts and accessories shall be deemed to be within the scope of this specification<br />
whether specifically mentioned or not.<br />
2.0 Service conditions<br />
2.1 The SCADA equipment may be installed any where in India. The<br />
equipment at RCC shall be installed indoors. Air-conditioning may be provided, if<br />
convenient, or else filtered air will be blown through to cool the equipments.<br />
2.2 The SCADA equipment at controlled stations shall be installed inside track<br />
side cubicles and subjected to vibrations on account of running trains on the near-by<br />
railway tracks. These cubicles will not be air-conditioned and are liable to exposure to<br />
polluted atmosphere.