6.1.3. Mimic diagram board (MDB)<br />
- 17 -<br />
6.1.3.1 A mimic diagram board and its associated mimic driver shall be provided<br />
at the RCC. The MDB shall depict the traction power supply diagram, indicating the<br />
energised/ de-energised condition of sub-sectors of catenary, status of interruptors and<br />
feeder circuit breakers at TSS & FP, SSP and SP.<br />
6.1.3.2 Since all control operations are to be carried out from the key board (s)<br />
provided at the workstation (s), the MDB‘s sole purpose is to give an overall view of the<br />
traction power supply system to the operator. In view of this limited function, the overall<br />
size of the MDB shall be restricted to 3500mm x 750mm x 200mm for depicting 30<br />
controlled stations.<br />
6.1.3.3 Annunciation for controlled stations<br />
For each controlled station an annunciation ―Remote station defective‖<br />
shall be provided on the MDB using an LED.<br />
6.1.3.4 Annunciations for master station equipment<br />
The following annunciations by LEDs shall be provided the MDB:<br />
i) Main system ON<br />
ii) Stand by system ON<br />
iii) Main system defective<br />
iv) Stand by system defective<br />
v) Main UPS sail<br />
vi) Stand by UPS fail<br />
vii) UPS battery low: This shall show up when the UPS<br />
battery voltage falls below 90% of the nominal voltage.<br />
Necessary relays/circuits for this purpose shall form part<br />
of the contract.<br />
viii) 415 V 3-phase ac to UPS fail<br />
6.1.3.5 Other facilities on the MDB<br />
The following facilities shall be provided on the MDB: