16.4.6 H19 (Indoor Fan Mo<strong>to</strong>r – DC Mo<strong>to</strong>r Mechanism Locked)<br />

Malfunction Decision Conditions<br />

The rotation speed detected by the Hall IC during fan mo<strong>to</strong>r operation is used <strong>to</strong> determine abnormal fan mo<strong>to</strong>r<br />

(feedback of rotation > 2550rpm or < 50rpm)<br />

Malfunction Caused<br />

Operation s<strong>to</strong>ps due <strong>to</strong> short circuit inside the fan mo<strong>to</strong>r winding.<br />

Operation s<strong>to</strong>ps due <strong>to</strong> breaking of wire inside the fan mo<strong>to</strong>r.<br />

Operation s<strong>to</strong>ps due <strong>to</strong> breaking of fan mo<strong>to</strong>r lead wires.<br />

Operation s<strong>to</strong>ps due <strong>to</strong> Hall IC malfunction.<br />

Operation error due <strong>to</strong> faulty indoor unit PCB.<br />

Troubleshooting<br />