10/154 NZM10, P10 circuit-breakers and switch-disconnectors<br />
Fault-current protection<br />
Circuit-breakers, switch-disconnectors<br />
up to 1600 A<br />
Residual-current relays<br />
Contact<br />
sequence<br />
R<strong>at</strong>ed control<br />
voltage<br />
U s<br />
V<br />
AC-sensitive<br />
R<strong>at</strong>ed fault current I Dn : 1 – 2.5 – 5 – 15 – 25 – 50 A,<br />
Delay time t v : 0, 50, 100, 150 ms,<br />
Both adjustable in stages<br />
– 230<br />
400<br />
– 415<br />
480<br />
<strong>For</strong> NZM circuitbreaker/switchdisconnector<br />
3-pole<br />
Type suffix<br />
Article no. for<br />
ordering with<br />
basic unit<br />
Price<br />
See Price<br />
List<br />
Type<br />
Article no. when<br />
ordered<br />
separ<strong>at</strong>ely<br />
NFI10-380<br />
044963<br />
NFI10-480<br />
044964<br />
– 680 NFI10-600<br />
044965<br />
– 500<br />
660<br />
– 230<br />
400<br />
– 415<br />
480<br />
4-pole<br />
NFI10-660<br />
044966<br />
NFI104-380<br />
044967<br />
NFI104-480<br />
044968<br />
– 600 NFI104-600<br />
044969<br />
– 500<br />
660<br />
NFI104-660<br />
044970<br />
Price<br />
See Price<br />
List<br />
<strong>Moeller</strong> HPL0211-2004/2005<br />
Std. pack<br />
1 off<br />
NFI10... residual-current relays<br />
Circuit diagram<br />
1)<br />
U<br />
U <<br />
12 14 11 D1 D2 C1 C2<br />
L1<br />
L2 L3 N<br />
I > I > I > I ><br />
NZM/ZM<br />
Oper<strong>at</strong>ion<br />
NFI core-balance transformers are used in conjunction with NZM circuit-breakers and<br />
switch-disconnectors. A secured control voltage, taken either directly from the input<br />
terminals of the NZM, or from an external source, is required to oper<strong>at</strong>e the electronic<br />
system of the residual-current relay. The electronic system of the residual-current<br />
relay issues the trip signal to the shunt release or undervoltage release of the NZM<br />
through a zero-voltage changeover contact. The switch then trips all poles in 0.2<br />
seconds or less. Fault signalling can be implemented via the auxiliary contact on the<br />
NZM. The built-in test button provides a simple means of functional testing, while an<br />
internal LED indic<strong>at</strong>es readiness for oper<strong>at</strong>ion. Monitoring is performed according to<br />
the oper<strong>at</strong>ing current principle. In the event of a power failure, the last oper<strong>at</strong>ional<br />
st<strong>at</strong>e is retained and is reapplied after voltage recovery.<br />
a<br />
b<br />
I<br />
N<br />
t V<br />
c<br />
d<br />
NFI<br />
TEST<br />
ON<br />
1) Route auxiliary power connections short-circuit proof<br />
<strong>For</strong> <strong>Immedi<strong>at</strong>e</strong> <strong>Delivery</strong> <strong>call</strong> <strong>KM<strong>Parts</strong></strong>.<strong>com</strong> <strong>at</strong> (866) 595-9616