10/154 NZM10, P10 circuit-breakers and switch-disconnectors<br />

Fault-current protection<br />

Circuit-breakers, switch-disconnectors<br />

up to 1600 A<br />

Residual-current relays<br />

Contact<br />

sequence<br />

R<strong>at</strong>ed control<br />

voltage<br />

U s<br />

V<br />

AC-sensitive<br />

R<strong>at</strong>ed fault current I Dn : 1 – 2.5 – 5 – 15 – 25 – 50 A,<br />

Delay time t v : 0, 50, 100, 150 ms,<br />

Both adjustable in stages<br />

– 230<br />

400<br />

– 415<br />

480<br />

<strong>For</strong> NZM circuitbreaker/switchdisconnector<br />

3-pole<br />

Type suffix<br />

Article no. for<br />

ordering with<br />

basic unit<br />

Price<br />

See Price<br />

List<br />

Type<br />

Article no. when<br />

ordered<br />

separ<strong>at</strong>ely<br />

NFI10-380<br />

044963<br />

NFI10-480<br />

044964<br />

– 680 NFI10-600<br />

044965<br />

– 500<br />

660<br />

– 230<br />

400<br />

– 415<br />

480<br />

4-pole<br />

NFI10-660<br />

044966<br />

NFI104-380<br />

044967<br />

NFI104-480<br />

044968<br />

– 600 NFI104-600<br />

044969<br />

– 500<br />

660<br />

NFI104-660<br />

044970<br />

Price<br />

See Price<br />

List<br />

<strong>Moeller</strong> HPL0211-2004/2005<br />

Std. pack<br />

1 off<br />

NFI10... residual-current relays<br />

Circuit diagram<br />

1)<br />

U<br />

U <<br />

12 14 11 D1 D2 C1 C2<br />

L1<br />

L2 L3 N<br />

I > I > I > I ><br />

NZM/ZM<br />

Oper<strong>at</strong>ion<br />

NFI core-balance transformers are used in conjunction with NZM circuit-breakers and<br />

switch-disconnectors. A secured control voltage, taken either directly from the input<br />

terminals of the NZM, or from an external source, is required to oper<strong>at</strong>e the electronic<br />

system of the residual-current relay. The electronic system of the residual-current<br />

relay issues the trip signal to the shunt release or undervoltage release of the NZM<br />

through a zero-voltage changeover contact. The switch then trips all poles in 0.2<br />

seconds or less. Fault signalling can be implemented via the auxiliary contact on the<br />

NZM. The built-in test button provides a simple means of functional testing, while an<br />

internal LED indic<strong>at</strong>es readiness for oper<strong>at</strong>ion. Monitoring is performed according to<br />

the oper<strong>at</strong>ing current principle. In the event of a power failure, the last oper<strong>at</strong>ional<br />

st<strong>at</strong>e is retained and is reapplied after voltage recovery.<br />

a<br />

b<br />

I<br />

N<br />

t V<br />

c<br />

d<br />

NFI<br />

TEST<br />

ON<br />

1) Route auxiliary power connections short-circuit proof<br />