10/184 Technical d<strong>at</strong>a<br />
Auxiliary contact, time differences<br />
Circuit-breakers, switch-disconnectors<br />
up to 1600 A<br />
At AC = 50/60 Hz M22-K... XHIV XHI<br />
Auxiliary contacts<br />
R<strong>at</strong>ed oper<strong>at</strong>ional voltage U e V AC 500 500 500<br />
R<strong>at</strong>ed oper<strong>at</strong>ional voltage U e V DC 220 220 220<br />
Conventional thermal current I th = I e A 4 4 4<br />
R<strong>at</strong>ed<br />
oper<strong>at</strong>ional<br />
current<br />
AC-15 115 V I e A 4 4 4<br />
230 V I e A 4 4 4<br />
400 V I e A 2 2 2<br />
500 V I e A 1 1 1<br />
DC-13 24 V I e A 3 3 3<br />
42 V I e A 1.7 1.5 –<br />
60 V I e A 1.2 0.8 1.2<br />
110 V I e A 0.8 0.5 0.5<br />
220 V I e A 0.3 0.2 0.2<br />
Short-circuit protection<br />
Max. fuse A gG/gL 10 10 10<br />
Max. mini<strong>at</strong>ure circuit-breaker A PKZM0-10/FAZ-B6 FAZ-B6 FAZ-B6<br />
Early make times <strong>com</strong>pared to main contacts during with<br />
make and break (switching times with manual<br />
oper<strong>at</strong>ion)<br />
Terminal<br />
capacity<br />
Solid or flexible conductor with ferrule mm 2 1 x (0.75 – 2.5)<br />
2 x (0.75 – 1.5)<br />
AWG 1 x (18 – 14)<br />
2 x (18 – 16)<br />
UL/CSA R<strong>at</strong>ed oper<strong>at</strong>ional current I e A 10 A – 600 V AC<br />
1 A – 250 V DC<br />
Heavy Pilot Duty<br />
A600/P300<br />
via 300 V AC same<br />
polarity<br />
ms – NZM1, PN1, N1: approx. –<br />
20<br />
NZM2, PN2, N2: approx.<br />
20<br />
NZM3, PN3, N3: approx.<br />
20<br />
NZM4, N4: approx. 90 1)<br />
1 x (0.75 – 2.5)<br />
2 x (0.75 – 1.5)<br />
1 x (18 – 14)<br />
2 x (18 – 16)<br />
2.5 A – 240 V AC<br />
1.0 A – 250 V DC<br />
C300/R300<br />
HPL0211-2004/2005<br />
1 x (0.75 – 2.5)<br />
2 x (0.75 – 1.5)<br />
1 x (18 – 14)<br />
2 x (18 – 16)<br />
2.5 A – 240 V AC<br />
1.0 A – 250 V DC<br />
C300/R300<br />
Notes<br />
1) With NZM4/N4 the HIV does not fe<strong>at</strong>ure early break.<br />
Time differences ON-OFF<br />
a<br />
b<br />
a<br />
b<br />
Time difference a (ms)<br />
Time difference b (ms)<br />
Manual oper<strong>at</strong>ion Motor oper<strong>at</strong>ors Manual oper<strong>at</strong>ion Motor oper<strong>at</strong>ors<br />
HIV HIN HIV HIN HIV HIN HIV HIN<br />
K10 K01 K10 K01 K10 K01 K10 K01<br />
NZM1 20 1) 0 2.5 – – – 20 1) 0 2.5 – – –<br />
NZM2 20 1) 3.5 6.5 Not permissible<br />
NZM3 20 1) 4 8 Not permissible<br />
NZM4 90 1) 7 11 Not permissible<br />
2.5 4.5 20 1) 3 4.5 Not permissible<br />
2 4 20 1) 3.5 8 Not permissible<br />
on request on request 0 1) 12 15 Not permissible<br />
3 4<br />
3 6.5<br />
on request on request<br />
Notes<br />
1) Minimum value, as it is dependent on the switching speed<br />
<strong>For</strong> <strong>Immedi<strong>at</strong>e</strong> <strong>Delivery</strong> <strong>call</strong> <strong>KM<strong>Parts</strong></strong>.<strong>com</strong> <strong>at</strong> (866) 595-9616