10/182 Technical d<strong>at</strong>a<br />

Switch-disconnectors<br />

Circuit-breakers, switch-disconnectors<br />

up to 1600 A<br />

PN1/N1<br />

160 A max.<br />

PN2/N2<br />

250 A max.<br />

<strong>Moeller</strong> HPL0211-2004/2005<br />

PN3/N3<br />

630 A max.<br />

N4<br />

1600 A max.<br />

Switch-disconnector:<br />

R<strong>at</strong>ed impulse withstand voltage<br />

U imp<br />

Main contacts V 6000 8000 8000 8000<br />

Auxiliary contacts V 6000 6000 6000 6000<br />

R<strong>at</strong>ed oper<strong>at</strong>ional voltage U e V AC 690 690 690 690<br />

R<strong>at</strong>ed uninterrupted current max.<br />

U imp<br />

IEC/EN 60947 I u A 160 250 630 1600<br />

UL 489, CSA 22.2 No. 5.1 I u A 125 250 600 1200<br />

Overvoltage c<strong>at</strong>egory/pollution degree III/3 III/3 III/3 III/3<br />

Switching capacity<br />

R<strong>at</strong>ed short-circuit making capacity I cm kA 2.8 5.5 25 53<br />

R<strong>at</strong>ed short-circuit making capacity t = 0.3 s I cw kA 2 3.5 12 25<br />

t = 1 s I cw kA 2 3.5 12 25<br />

R<strong>at</strong>ed conditional short-circuit current<br />

A gG/gL 125<br />

250 630 2 x 800<br />

with back-up fuse<br />

PN1(N1) – 160: 160<br />

400/415 V kA 100 100 100 100<br />

690 V kA 100 30 50 80<br />

R<strong>at</strong>ed making and breaking capacity<br />

R<strong>at</strong>ed oper<strong>at</strong>ional current 415 V I e A 160 250 630 1600<br />

AC-22/23A<br />

690 V I e A 160 250 630 1600<br />

Lifespan, mechanical Oper<strong>at</strong>ions 20000 20000 15000 10000<br />

Maximum oper<strong>at</strong>ing frequency Ops/h 120 120 60 60<br />

Lifespan, electrical AC-1 400/415 V Oper<strong>at</strong>ions 10000 10000 5000 3000<br />

690 V Oper<strong>at</strong>ions 7500 7500 3000 2000<br />

AC-3 400/415 V Oper<strong>at</strong>ions 7500 7500 3000 2000<br />

690 V Oper<strong>at</strong>ions 5000 5000 2000 1000<br />

Current he<strong>at</strong> loss per pole <strong>at</strong> I u W 8 16 40 97<br />

NZM1, PN1, N1 NZM2, PN2, N2<br />

250 A<br />

125 A 160 A without with XSV<br />

XSV TM<br />

E<br />

NZM3, PN3, N3<br />

630 A<br />

without with XAV<br />

XAV<br />

NZM4, N4<br />

1600 A<br />

without<br />

XAV<br />

with XAV<br />

Permissible loading with varying ambient<br />

temper<strong>at</strong>ures<br />

Open 20 °C % 100 100 100 100 100 100 96 100 100<br />

30 °C % 100 100 100 97 100 100 92 100 98<br />

40 °C % 100 100 100 92 100 100 87 100 93<br />

50 °C % 100 95 100 87 94 100 83 100 89<br />

60 °C % 86 90 90 81 88 90 78 87 85<br />

65 °C % 83 85 85 78 84 85 75 85 83<br />

70 °C % 79 80 80 75 81 80 73 82 80<br />

Notes<br />

XSV = plug-in unit, XAV = withdrawable unit<br />

TM = thermomagnetic, E = electronic<br />

Plug-in units NZM...2-A(M)(S)...250 +<br />

NZM2-XSV<br />

N2-...250 + NZM2-XSV<br />

NZM...2-VE...250 +<br />

NZM2-XSV<br />

NZM...2-ME...220 +<br />

NZM2-XSV<br />

NZM...2-4-A...250 +<br />

NZM2-4-XSV<br />

N2-4-...250 +<br />

NZM2-4-XSV<br />

NZM...2-4-VE...250 +<br />

NZM2-4-XSV<br />

Effective power loss<br />

40 A W 14 – – 14 –<br />

50 A W 19 – – 19 –<br />

63 A W 22 – – 22 –<br />

80 A W 24 – – 24 –<br />

90 A W - – 10 – –<br />

125 A W 34 – – 34 31<br />

140 A W – – 24 – –<br />

160 A W 48 31 – 48 31<br />

200 A W 60 40 – 60 40<br />

220 A W – – 59 – –<br />

230 A W 64 – – 64 –<br />

250 A W – 76 – – 76<br />

<strong>For</strong> <strong>Immedi<strong>at</strong>e</strong> <strong>Delivery</strong> <strong>call</strong> <strong>KM<strong>Parts</strong></strong>.<strong>com</strong> <strong>at</strong> (866) 595-9616