10/28<br />

Overview<br />

Circuit-breakers, switch-disconnectors for North America, 3-pole<br />

Overview<br />

Circuit-breakers, switch-disconnectors for North America, 3-pole<br />

10/29<br />

Circuit-breakers, switch-disconnectors<br />

up to 1600 A<br />

Circuit-breakers<br />

UL/CSA approved to UL<br />

489, CSA 5<br />

and to IEC/EN 60947<br />

<strong>Moeller</strong> HPL0211-2004/2005<br />

<strong>Moeller</strong> HPL0211-2004/2005<br />

R<strong>at</strong>ed uninterrupted current I u = r<strong>at</strong>ed current I n<br />

Thermomagnetic releases Electronic releases<br />

Delayed short-circuit release I sd<br />

Fixed Adjustable Without Fixed Adjustable Without Fixed Adjustable Without Fixed Adjustable System protection Motor<br />

Adjustable overload release I r<br />

Adjustable short-circuit release I i<br />

Overload releases Overload releases Short-circuit releases<br />

protection<br />

I u I u I r I u I u I u I r I u I u I u I r I u I u I u I r I sd I i I i<br />

A A A A A A A A A A A A A A A A A A<br />

NZM1 NZM2 NZM1 NZM2 NZM1 NZM2<br />

Circuit-breakers, switch-disconnectors<br />

up to 1600 A<br />

15 – 125 15 – 250 20 – 125 20 – 250 0.8 – 1 x I n 1 – 100 1.6 – 200 150 –<br />

250<br />

100 –<br />

250<br />

0.5 – 1 x I n 90 –<br />

220<br />

250 –<br />

600<br />

250 –<br />

600<br />

0.5 – 1 x I n 220 –<br />

450<br />

Basic switching capacity 1) NZMB1-...-NA NZMB2-...-NA<br />

NEMA Test Procedure 240 V 60 Hz sym. rms kA 35 4) 35<br />

480 V 60 Hz sym. rms kA 25 2) 25 2)<br />

600 V 60 Hz sym. rms kA – 18 3)<br />

IEC/EN 60947 400/415 V kA/cos v 25 0.25 25 0.25<br />

440 V kA/cos v 25 0.25 25 0.25<br />

525 V kA/cos v 15 0.30 15 0.30<br />

Normal switching capacity 1) NZMN1-...-NA NZMN2-...-NA NZMN2-...E...-NA NZMN3-...E...-NA NZMN4-...E...-NA<br />

NEMA Test Procedure 240 V 60 Hz sym. rms kA 85 5) 85 85 85 85<br />

480 V 60 Hz sym. rms kA 35 2) 35 2) 35 2) 35 35<br />

600 V 60 Hz sym. rms kA – 25 3) 25 3) 25 25<br />

IEC/EN 60947 400/415 V kA/cos v 50 0.25 50 0.25 50 0.25 50 0.25 50 0.25<br />

440 V kA/cos v 35 0.25 35 0.25 35 0.25 35 0.25 35 0.25<br />

525 V kA/cos v 20 0.30 25 0.25 25 0.25 25 0.25 25 0.25<br />

690 V kA/cos v 10 0.50 20 0.30 20 0.30 20 0.30 20 0.30<br />

High switching capacity 1) NZMH2-...-NA NZMH2-...E...-NA NZMH3-...E...-NA NZMH4-...E...-NA<br />

NEMA Test Procedure 240 V 60 Hz sym. rms kA 100 100 100 100<br />

480 V 60 Hz sym. rms kA 65 2) 65 2) 65 65<br />

600 V 60 Hz sym. rms kA 35 3) 35 3) 35 35<br />

IEC/EN 90947 400/415 V kA/cos v 100 0.20 100 0.20 100 0.20 100 6) 0.20<br />

440 V kA/cos v 65 0.20 65 0.20 65 0.20 65 0.20<br />

525 V kA/cos v 40 0.25 40 0.25 40 0.25 40 0.25<br />

690 V kA/cos v 20 0.30 20 0.30 20 0.30 35 0.25<br />

Limiter switching capacity 1) NZML3-...E...-NA NZML4-...E...-NA<br />

NEMA Test Procedure 240 V 60 Hz sym. rms kA 150 150<br />

480 V 60 Hz sym. rms kA 100 100<br />

600 V 60 Hz sym. rms kA 50 50<br />

IEC/EN 90947 400/415 V kA/cos v 150 0.20 120 6)7) 0.20<br />

440 V kA/cos v 130 0.20 85 0.20<br />

525 V kA/cos v 65 0.20 65 0.20<br />

690 V kA/cos v 35 0.25 50 0.25<br />

600 –<br />

1200<br />

800 –<br />

1200<br />

0.5 – 1 x I n 2 – 10 x I r 2 – 12 x I n 2 – 14 x I r<br />

Notes<br />

Values printed in grey available on request<br />

1)The switches conform to the UL/CSA and also to the IEC regul<strong>at</strong>ions<br />

IEC switching values contained on the r<strong>at</strong>ing label. a Technical d<strong>at</strong>a<br />

2) With NZM...1-...-NA and NZM...2-...-NA the following applies: 480Y/277 V probably until October 2004<br />

3) With NZM...2-...-NA the following applies: 600V on request<br />

4) With NZMB1-...-NA the following applies: 25 kA probably until October 2004<br />

5) With NZMN1-...-NA the following applies: 35 kA probably until October 2004<br />

6) With NZM(H)L4-... the following applies: 85 kA probably until October 2004<br />

7) 100 kA from October 2004, 120 kA in prepar<strong>at</strong>ion<br />

The approved switches are suitable for world-wide use. The UL and CSA certific<strong>at</strong>es can be found <strong>at</strong> www.ul.<strong>com</strong> and www.csa.<strong>com</strong><br />

UL certific<strong>at</strong>e: File No.: E 31593 (NZM1-4)<br />

CSA certific<strong>at</strong>es: File No. NZM1: 165628-...(NZM1-4)<br />

Switch-disconnector:<br />

with main switch and isol<strong>at</strong>ing characteristics<br />

without overload and short-circuit release<br />

R<strong>at</strong>ed uninterrupted current I u = I n<br />

UL/CSA approved to UL<br />

489, CSA 5<br />

and to IEC/EN 60947<br />

63 160 800<br />

100 200 400 1000<br />

125 250 600 1200<br />

N1-...-NA N2-...-NA N3-...-NA N4-...-NA<br />

R<strong>at</strong>ed short-circuit making capacity I cm kA 2.8 5.5 25 53<br />

R<strong>at</strong>ed short time current I cw (1s current rms ) kA 2 3.5 12.5 25<br />

<strong>For</strong> <strong>Immedi<strong>at</strong>e</strong> <strong>Delivery</strong> <strong>call</strong> <strong>KM<strong>Parts</strong></strong>.<strong>com</strong> <strong>at</strong> (866) 595-9616