10/188 Technical d<strong>at</strong>a<br />
D<strong>at</strong>a Management Interface (DMI Module)<br />
Circuit-breakers, switch-disconnectors<br />
up to 1600 A<br />
<strong>Moeller</strong> HPL0211-2004/2005<br />
General<br />
Dimensions (W x H x D) mm 107.5 x 90 x 53<br />
Modular spacing (space units)<br />
6 space units wide<br />
Weight kg 0.3<br />
Mounting<br />
Mounting rail according to IEC/EN 60715, 35 mm<br />
Clim<strong>at</strong>ic environmental conditions<br />
Oper<strong>at</strong>ing ambient temper<strong>at</strong>ure °C 0 to +55<br />
Mounting position<br />
horizontalxvertical<br />
Condens<strong>at</strong>ion<br />
Prevent condens<strong>at</strong>ion by means of suitable measures<br />
LCD display (clearly legible) °C 0 to +55<br />
Storage/transport °C -40 to +70<br />
Rel<strong>at</strong>ive humidity, non-condensing (IEC/EN 60068-2-30) % 5 – 95<br />
Atmospheric pressure (oper<strong>at</strong>ion) hPa 795 – 1080<br />
Corrosion resistance<br />
IEC/EN 60947-2-42 4 days SO 2 cmC/mC 10<br />
IEC/EN 60068-2-43 4 days H 2 S cmC/mC 1<br />
Ambient conditions, mechanical<br />
Pollution degree 2<br />
Degree of protection (IEC/EN 60529)<br />
IP20<br />
Vibr<strong>at</strong>ions (IEC/EN 60068-2-6)<br />
Constant amplitude 0.15 mm Hz 10 – 57<br />
Constant acceler<strong>at</strong>ion, 2 g Hz 57 – 150<br />
Mechanical shock resistance (IEC/EN 60068-2-27)<br />
Impacts 18<br />
semi-sinusoidal 15 g/11 ms<br />
Drop to IEC/EN 60068-2-31 Drop height mm 50<br />
Free fall, packaged (IEC/EN 60068-2-32) m 1<br />
Power supply<br />
R<strong>at</strong>ed oper<strong>at</strong>ional voltage U e V DC 24<br />
Admissible range V DC 20.4 – 28.8<br />
Residual ripple % F5<br />
Input current <strong>at</strong> 24 V DC mA 210<br />
Voltage dips (IEC/EN 61131-2) ms 10<br />
He<strong>at</strong> dissip<strong>at</strong>ion <strong>at</strong> 24 V DC W 5<br />
Type Weight Type Weight<br />
kg<br />
kg<br />
Circuit-breakers<br />
Switch-disconnector:<br />
NZM...1-... 1.046 PN1-..., N1-... 0.926<br />
NZM...1-4-... 1.325 PN1-4-..., N1-4-... 1.325<br />
NZM...2-... 2.345 PN2-..., N2-... 2.15<br />
NZM...2-4-... 3.5 PN2-4-..., N2-4-... 2.65<br />
NZM...3-... 6.34 PN3-..., N3-... 5.7<br />
NZM...3-4-... 8.4 PN3-4-..., N3-4-... 7.1<br />
NZM...4-... 21 N4-... 17<br />
NZM...4-4-... 27 N4-4-... 22<br />
Plug-in adapter elements<br />
+NZM2-XSV 4.7<br />
+NZM2-4-XSV 5.9<br />
Withdrawable unit<br />
+NZM3-XAV 21<br />
+NZM3-4-XAV 27<br />
+NZM4-XAV 52<br />
+NZM4-4-XAV 65<br />