10/118<br />

P7 switch-disconnectors, 3-pole<br />

Safety switches, 63 – 250 A<br />

P7 switch-disconnectors, 3-pole<br />

Safety switches, 63 – 250 A<br />

10/119<br />

Circuit-breakers, switch-disconnectors<br />

up to 1600 A<br />

Contact sequence Contact sequence R<strong>at</strong>ed<br />

uninterrupted<br />

current<br />

Motor r<strong>at</strong>ing AC-23<br />

220 V<br />

230 V<br />

240 V<br />

380 V<br />

400 V<br />

415 V<br />

500 V 660 V<br />

690 V<br />

I u P P P P<br />

A kW kW kW kW<br />

<strong>Moeller</strong> HPL0211-2004/2005<br />

<strong>For</strong> use as Emergency-Stop device<br />

According to IEC/EN 60204-1, VDE 0113<br />

Part 1<br />

With red-yellow door coupling rotary<br />

handle<br />

Lockable in 0 position,<br />

With cover interlock<br />

Degree of protection IP55.<br />

Type<br />

Article no.<br />

Price<br />

See Price List<br />

<strong>Moeller</strong> HPL0211-2004/2005<br />

Without Emergency-Stop function<br />

With grey door coupling rotary handle,<br />

Lockable in 0 position,<br />

With cover interlock<br />

Degree of protection IP55.<br />

Type<br />

Article no.<br />

Price<br />

See Price List<br />

Std. pack<br />

Enclosure description<br />

insul<strong>at</strong>ed enclosure<br />

Terminals for 5th<br />

conductor (neutral<br />

pole) for fitting by user<br />

Notes<br />

Circuit-breakers, switch-disconnectors<br />

up to 1600 A<br />

Safety switches<br />

LA M<br />

L1 L2 L3 3.14 1.14 1.24<br />

3.13 1.13 1.23<br />

L1 L2 L3<br />

3.14-1.14<br />

1.24-1.23<br />

L1 L2 L3<br />

3.14-1.14<br />

1.24-1.23<br />

63 15 30 37 55 P7-63/CI-RT-SI/LAM<br />

225514<br />

100 30 45 55 90 P7-100/CI-RT-SI/LAM<br />

225515<br />

160 45 75 110 132 P7-160/CI-RT-SI/LAM<br />

225516<br />

200 55 90 132 160 P7-200/CI-RT-SI/LAM<br />

225517<br />

250 70 110 160 215 P7-250/CI-RT-SI/LAM<br />

225518<br />

P7-63/CI-SI/LAM<br />

225519<br />

P7-100/CI-SI/LAM<br />

225520<br />

P7-160/CI-SI/LAM<br />

225521<br />

P7-200/CI-SI/LAM<br />

225522<br />

P7-250/CI-SI/LAM<br />

225523<br />

1 off CI23-150 + 2 x FL2-3 K25/1 Enclosures for separ<strong>at</strong>e mounting, with cable entry. Include<br />

fixing straps for wall mounting.<br />

KST34–150+KS3 K95/1N/BR<br />

Only for switches with terminals.<br />

Degree of protection IP55.<br />

KST34–150+KS3 K95/1N/BR<br />

Not in <strong>com</strong>bin<strong>at</strong>ion with remote oper<strong>at</strong>or.<br />

KST34–150+KS3<br />

CI45-200 + 2 x KS4<br />

K95/1N/BR<br />

K150/1/BR<br />

Notes<br />

Engineering notes<br />

Fe<strong>at</strong>ures<br />

Maintenance, repair and safety switches all<br />

have the same electrical function. They are<br />

designed to safely isol<strong>at</strong>e electrical<br />

install<strong>at</strong>ions (loads) from mains power during<br />

maintenance and repair work and to ensure<br />

th<strong>at</strong> a hazard does not arise which endangers<br />

personnel, machinery and production<br />

m<strong>at</strong>erials.<br />

Safety switches are main switches with an<br />

additional enclosure. Installed in the<br />

immedi<strong>at</strong>e vicinity of the motor or the<br />

electrical load they act as switchdisconnectors<br />

for th<strong>at</strong> load. Provided the five<br />

safety rules defined in VDE 0105 are observed,<br />

they should ensure a safe working<br />

environment. This is particularly important if<br />

there is any danger of the main switch being<br />

inadvertently oper<strong>at</strong>ed.<br />

Applic<strong>at</strong>ion<br />

By securing the switch in the OFF position with<br />

his own padlock (up to three can be fitted), the<br />

fitter/electrician can protect himself against<br />

the possibility of any other person switching<br />

the machine on.<br />

Maintenance switches are merely additional,<br />

enclosed main switches with a padlocking<br />

facility.<br />

Safety switches are housed in insul<strong>at</strong>ed<br />

enclosures and bear the inscription “Safety<br />

switch” on a bright orange label. Labels are<br />

available in other languages.<br />

Switches to be used as Emergency-Stop<br />

devices have a special red handle with a<br />

yellow locking collar in accordance with STOP<br />

c<strong>at</strong>egory 0 as defined by IEC/EN 60204. If the<br />

switch is not approved as an Emergency-Stop<br />

switch, both parts are grey.<br />

The cover and handle can be interlocked by<br />

fitting a padlock.<br />

Selection<br />

Switches must be selected according to the<br />

following criteria:<br />

• The motor switching capacity, where the<br />

switch is fitted in such a way th<strong>at</strong> the<br />

oper<strong>at</strong>or may use it for oper<strong>at</strong>ional ON and<br />

OFF switching.<br />

• The r<strong>at</strong>ing d<strong>at</strong>a always applies for 3 poles.<br />

When the motor r<strong>at</strong>ing is divided between 6<br />

poles, such as for star-delta switching, a 6-<br />

pole switch can be used to control 1.73<br />

times the r<strong>at</strong>ed power.<br />

• If the switch has a load-shedding contact<br />

(LA), you can select the appropri<strong>at</strong>e switch<br />

according to the uninterrupted current. The<br />

load-shedding contact is an auxiliary<br />

contact, which is closed in the ON position<br />

and opens early when switching off, so th<strong>at</strong><br />

a contactor loc<strong>at</strong>ed in the circuit takes over<br />

the switching capacity and the<br />

maintenance/safety switch oper<strong>at</strong>es <strong>at</strong> zero<br />

load. When switching on, the load-shedding<br />

contact closes l<strong>at</strong>er than or <strong>at</strong> the same time<br />

as the main contacts. This is achieved by<br />

connecting an early-make auxiliary contact<br />

(VHI) and a standard auxiliary contact (NHI)<br />

in series.<br />

• If the switch is prevented from switching<br />

under load, you can also select it according<br />

to the continuous current. With a suitable<br />

handle and collar, you can, for example,<br />

lock the switch in its ON position. This is not<br />

permissible for switches with a red/yellow<br />

handle.<br />

Safety switch with load shedding and annunci<strong>at</strong>ion (example)<br />

L1<br />

L2<br />

L3<br />

PEN<br />

Q 100<br />

K10<br />

Safety switch<br />

Q10<br />

0 I<br />

1<br />

2<br />

3<br />

4<br />

M<br />

3~<br />

5<br />

6<br />

VHI<br />

NHI<br />

LA<br />

M<br />

H10<br />

F1<br />

Q100-S1<br />

0<br />

S10<br />

I<br />

K10<br />

K10<br />

<strong>For</strong> <strong>Immedi<strong>at</strong>e</strong> <strong>Delivery</strong> <strong>call</strong> <strong>KM<strong>Parts</strong></strong>.<strong>com</strong> <strong>at</strong> (866) 595-9616