Design rules<br />
Protection index<br />
The various IK codes and their meaning<br />
IK code IK 01 IK 02 IK 03 IK 04 IK 05 IK 06 IK 07 IK 08 IK 09 IK 10<br />
energies in joules 0.15 0.2 0.35 0.5 0.7 1 2 5 10 20<br />
radius mm 1 10 10 10 10 10 10 25 25 50 50<br />
material 1 P P P P P P A A A A<br />
steel = A 2<br />
polyamide = P 3<br />
hammer<br />
pendulum ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔<br />
spring loaded 4 ✔ ✔ ✔ ✔ ✔ ✔<br />
vertical ✔ ✔ ✔ ✔<br />
✔ = yes<br />
N.B.:<br />
1<br />
of the hammer head<br />
2<br />
Fe 490-2 according to ISO 1052, hardness 50 HR to 58 HR according to ISO 6508<br />
3<br />
hardness HR 100 according to ISO 2039-2<br />
44 Merlin Gerin <strong>MV</strong> <strong>design</strong> <strong>guide</strong> <strong>Schneider</strong> <strong>Electric</strong>