Standards<br />

IEC - ANSI comparison<br />

According to ANSI<br />

c The circuit breaker must be able to break:<br />

v the rated short circuit current at the rated maximum voltage<br />

v K times the rated short-circuit current (maxi symmetrical interrupting<br />

capability with K: voltage range factor) at the operating voltage (maximum<br />

voltage/K)<br />

v between the two currents obtained by the equation:<br />

maxi symetrical current<br />

rated short-circuit current<br />

rated maxi voltage<br />

= = K<br />

rated voltage<br />

We therefore have a constant breaking power (in <strong>MV</strong>A) over a given<br />

voltage range. Moreover, the asymmetrical current will be a function of the<br />

following table taking S = 1.1 for Merlin Gerin circuit breakers.<br />

1.8<br />

1.7<br />

1.6<br />

1.5<br />

1.4<br />

1.3<br />

1.2<br />

1.1<br />

1<br />

ratio S<br />

Asymmetrical interrupting capability = S x symetrical interrupting capability.<br />

Both at specified operating voltage<br />

Symetrical interrupting capability at<br />

specified operating voltage = 1.0<br />

0 0.5 1 2 3 4<br />

cycles<br />

0 0.006 0.017 0.033 0.050 0.067 seconds<br />

Example:<br />

c Isc = 40 kA<br />

c % asymmetry = 50%<br />

c Iasym = 1.1 • 40 = 44 kA<br />

44 44<br />

c Isym = = = 36 kA<br />

1 + 2(50%) 2 1,22<br />

Sequence 6 will therefore be tested at<br />

36 kA + 50% asymmetry,<br />

this being 44 kA of total current.<br />

c Rated short-circuit breaking capacity (kA)<br />

Sequence n° current broken % aperiodic component<br />

1 10 50 - 100<br />

2 30 < 20<br />

3 60 50 - 100<br />

4 100 < 20<br />

5 KI to V/K < 20<br />

6 SI to V 50 - 100<br />

7 KSI to V/K 50 - 100<br />

8 electrical endurance<br />

9/10 reclosing cycle at ASI and AKSI<br />

11 C - 2 s - O at KI<br />

12 rated Isc duration = KI for 3 s<br />

13/14 single phase testing at KI and KSI (0.58 V)<br />

Short-circuit breaking testing must comply with the<br />

14 test sequences above, with:<br />

I : symmetrical breaking capacity at maximum voltage<br />

R : reclosing cycle coefficient<br />

(Reclosing factor)<br />

K : voltage range factor:<br />

K = Vmax<br />

Vmin<br />

Iasym<br />

S : asymmetrical factor: = 1.1<br />

Isym<br />

for Merlin Gerin circuit breakers<br />

V : maximum rated voltage<br />

76 Merlin Gerin <strong>MV</strong> Design Guide <strong>Schneider</strong> <strong>Electric</strong>