Switchgear<br />
definition<br />
Current transformer<br />
Differential protection<br />
Many manufacturers of differential protection relays recommend<br />
class X CT's.<br />
c Class X is often requested in the form of:<br />
Vk ≤ a . If (Rct + Rb + Rr)<br />
The exact equation is given by the relay manufacturer.<br />
Values characterising the CT<br />
Vk : Knee-point voltage in volts<br />
a : asymmetry coefficient<br />
Rct : max. resistance in the secondary winding in Ohms<br />
Rb : loop resistance (feed/return line) in Ohms<br />
Rr : resistance of relays not located in the differential part<br />
of the circuit in Ohms<br />
If : maximum fault current seen by the CT<br />
in the secondary circuit for a fault outside of the zone<br />
to be protected<br />
If = Isc<br />
Kn<br />
Isc : primary short-circuit current<br />
Kn : CT transformation ratio<br />
What values should If be given to determine Vk?<br />
c The short-circuit current is chosen as a function of the application:<br />
v generator set differential<br />
v motor differential<br />
v transformer differential<br />
v busbar differential.<br />
c For a generator set differential:<br />
v if Isc is known: Isc short-circuit current for the generator set on its own<br />
If = Isc<br />
Kn<br />
relay<br />
CT G CT<br />
v if the Ir gen is known: we will take<br />
If =<br />
7 • Ir gen<br />
Kn<br />
v if the Ir gen is unknown: we will take<br />
If = 7 • Isr (CT)<br />
Isr(CT) = 1 or 5 A<br />
c For motor differential:<br />
v if the start-up current is known: we will take<br />
Isc = I start-up<br />
relay<br />
CT M CT<br />
If = Isc<br />
Kn<br />
v if the Ir motor is known: we will take<br />
If = 7 • Ir<br />
Kn<br />
v if the Ir motor is not known: we will take<br />
If = 7 • Isr (CT)<br />
Isr(TC) = 1 or 5 A<br />
Reminder<br />
Ir : rated current<br />
<strong>Schneider</strong> <strong>Electric</strong><br />