Standards<br />

IEC - ANSI comparison<br />

The following comparison<br />

is based on<br />

different circuit breaker<br />

characteristics.<br />

Overview of the main differences<br />

Theme ANSI IEC<br />

asymmetrical breaking 50% 30%<br />

capacity on faults with current without derating<br />

across the terminals derating<br />

insulation level:<br />

imposes chopped waves<br />

impulse wave<br />

for outdoor equipment<br />

115% Uw/3 s<br />

129% Uw/2 s<br />

short-time withstand 2.7 Isc 2.5•Isc at 50 Hz<br />

current peak<br />

2.6•Isc at 60 Hz<br />

value<br />

2.7•Isc for special cases<br />

Transient Recovery around twice<br />

voltage (1)<br />

as severe<br />

electrical endurance 4 times K.S.Isc 3 times Isc<br />

mechanical endurance 1 500 to 10 000 2 000<br />

according to Ua and Isc<br />

motor overvoltages no text standard test circuit<br />

(1)<br />

the ANSI peak voltage is 10% greater than the voltage defined by the IEC.<br />

The E2/t2 slope is 50% greater than the Uc/t3 slope.<br />

However, the largest part of the graph is the initial part where the SF6 reconstitutes itself.<br />

The two standards easily allow the SF6 to reconstitute itself.<br />

Rated voltages<br />

According to IEC<br />

c Standardised values for Ur (kV): 3.6 - 7.2 - 12 - 17.5 - 24 - 36 kV<br />

According to ANSI<br />

c The ANSI standard defines a class and a voltage range factor K<br />

which defines a range of rated voltages at constant power.<br />

Standardised values for Ur (kV)<br />

class (kV) Umax (kV) Umin (kV) K<br />

Indoor equipment 4.16 4.76 3.85 1.24<br />

7.2 8.25 6.6 1.25<br />

13.8 15 11.5 1.3<br />

38 38 23 1.65<br />

Outdoor equipment 15.5 1<br />

25 1<br />

38 1<br />

100<br />

90<br />

50<br />

10<br />

Upeak (%)<br />

1.2 µs<br />

50 µs<br />

Standardised wave 1.2/50 µs<br />

t (µs)<br />

Rated installation level<br />

According to IEC<br />

Rated Rated lightning Rated power frequency<br />

voltage withstand voltage withstand voltage<br />

(kV) (kV) 50 Hz 1 mm (kV)<br />

7.2 60 20<br />

12 75 28<br />

17.5 95 38<br />

24 125 50<br />

36 170 70<br />

72 Merlin Gerin <strong>MV</strong> Design Guide <strong>Schneider</strong> <strong>Electric</strong>