Switchgear<br />
definition<br />
Current transformer<br />
CT<br />
CT<br />
relay<br />
c For a transformer differential<br />
The Isc to take is that flowing through the CT's for a current consumer side<br />
fault. In all cases, the fault current value If is less than 20 Isr(CT).<br />
v if we do not know the exact value, we will take:<br />
If = 20 Isr(CT)<br />
c For busbar differential<br />
v the Isc to take is the switchboard Ith<br />
If = Ith<br />
Kn<br />
c For a line differential<br />
The Isc to take is the Isc calculated at the other end of the line, therefore<br />
limited by the cable impedance. If the impedance of the cable is not<br />
known, we will take the switchboard Ith.<br />