Switchgear<br />

definition<br />

Medium voltage circuit breaker<br />

c Value of rated TRV<br />

v the TRV is a function of the asymmetry, it is given for an asymmetry of 0%.<br />

Uc<br />

U (kV)<br />

Rated TRV Time Delay Increase<br />

voltage value rate<br />

(Ur in kV) (Uc in kV) (t3 in µs) (td in µs) (Uc/td in kV/µs)<br />

7.2 12.3 52 8 0.24<br />

12 20.6 60 9 0.34<br />

17.5 30 72 11 0.42<br />

24 41 88 13 0.47<br />

36 62 108 16 0.57<br />

td<br />

0<br />

t3<br />

t (µs)<br />

r<br />

Uc = 1.4 • 1.5 • • Ur = 1.715 Ur<br />

e<br />

td = 0.15 t3<br />

v a specified TRV is represented by a reference plot with two parameters<br />

and by a segment of straight line defining a time delay.<br />

Td : time delay<br />

t3 : time defined to reach Uc<br />

Uc : peak TRV voltage in kV<br />

TRV increase rate:<br />

Uc/t3 in kV/µs<br />

X1<br />

A<br />

B<br />

X2<br />

Rated out-of-phase breaking current<br />

(cf. § 4.106 IEC 60 056)<br />

When a circuit breaker is open and the conductors are not synchronous,<br />

the voltage across the terminals can increase up the sum of voltages in<br />

the conductors (phase opposition).<br />

G<br />

U1<br />

U2<br />

G<br />

c In practice, standards require the circuit breaker to break a current<br />

equal to 25% of the fault current across the terminals, at a voltage<br />

equal to twice the voltage relative to earth.<br />

UA - UB = U1 - (-U2) = U1 + U2<br />

si U1 = U2 so UA - UB = 2U<br />

c If Ur is the rated circuit breaker voltage, the recovery voltage (TRV) at<br />

power frequency is equal to:<br />

v 2e Ur for networks with a neutral earthing arrangement<br />

v 2.5e Ur for other networks.<br />

c Peak values for TRV for networks other than those with neutral earthing:<br />

e<br />

Uc = 1.25 • 2.5 • • Ur<br />

r<br />

Rated TRV Time Rate of<br />

voltage value increase<br />

(Ur in kV) (Uc in kV) (t3 in µs) (Uc/td in kV/µs)<br />

7.2 18.4 104 0.18<br />

12 30.6 120 0.26<br />

17.5 45 144 0.31<br />

24 61 176 0.35<br />

36 92 216 0.43<br />

50 Merlin Gerin <strong>MV</strong> <strong>design</strong> <strong>guide</strong> <strong>Schneider</strong> <strong>Electric</strong>