23.02.2014 Views

MV design guide - Schneider Electric

MV design guide - Schneider Electric

MV design guide - Schneider Electric

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

Switchgear<br />

definition<br />

Derating<br />

Introduction<br />

The various standards or recommendations impose validity limits on<br />

device characteristics.<br />

Normal conditions of use are described in the "Medium voltage circuit<br />

breaker" chapter.<br />

Beyond these limits, it is necessary to reduce certain values, in other<br />

words to derate the device.<br />

c Derating must be considered:<br />

v in terms of the insulation level, for altitudes of over 1 000 metres<br />

v in terms of the rated current, when the ambient temperature exceeds<br />

40°C and for a protection index of over IP3X,<br />

(see chapter on "Protection indices").<br />

These different types of derating can be accumulated if necessary.<br />

N.B.: there are no standards specifically dealing with derating.<br />

However, table V § 442 of IEC 60 694 deals with temperature rises and gives limit temperature<br />

values not to be exceeded according to the type of device, the materials and the dielectric<br />

used.<br />

Example of application:<br />

Can equipment with a rated voltage<br />

of 24 kV be installed at 2500 metres?<br />

The impulse withstand voltage required is<br />

125 kV.<br />

The power frequency withstand 50 Hz is<br />

50 kV. 1 mn.<br />

c For 2500 m:<br />

v k is equal to 0.85<br />

v the impulse withstand must be<br />

125/0.85 = 147.05 kV<br />

v the power frequency withstand 50 Hz<br />

must be 50/0.85 = 58.8 kV<br />

c No, the equipment that must be<br />

installed is:<br />

v rated voltage = 36 kV<br />

v impulse withstand = 170 kV<br />

v withstand at 50 Hz = 70 kV<br />

Insulation derating according<br />

to altitude<br />

Standards give a derating for all equipment installed at an altitude<br />

greater than 1 000 metres.<br />

As a general rule, we have to derate by 1.25 % U peak every 100 metres<br />

above 1 000 metres.<br />

This applies for the lightning impulse withstand voltage and the power<br />

frequency withstand voltage 50 Hz - 1 mn. Altitude has no effect on the<br />

dielectric withstand of circuit breakers in SF6 or vacuum, because they<br />

are within a sealed enclosure. Derating, however, must be taken account<br />

of when the circuit breaker is installed in cubicles. In this case, insulation<br />

is in air.<br />

c Merlin Gerin uses correction coefficients:<br />

v for circuit breakers outside of a cubicle, use the graph below<br />

v for circuit breakers in a cubicle, refer to the cubicle selection <strong>guide</strong><br />

(derating depends on the cubicle <strong>design</strong>).<br />

Exception of the Mexican market: derating starts from zero metres<br />

(cf. dotted line on the graph below).<br />

N.B.:<br />

if you do not want to supply 36 kV equipment,<br />

we must have the appropriate test certificates<br />

proving that our equipment complies with the<br />

request.<br />

1<br />

0.9<br />

0.8<br />

0.7<br />

0.6<br />

Correctilon coefficient k<br />

0.5<br />

0 1000 2000 3000 4000 5000<br />

altitude in m<br />

64 Merlin Gerin <strong>MV</strong> <strong>design</strong> <strong>guide</strong> <strong>Schneider</strong> <strong>Electric</strong>

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!