Switchgear<br />

definition<br />

Voltage transformer<br />

We can leave a<br />

voltage transformer in an<br />

open circuit without any danger<br />

but it must never be<br />

short-circuited.<br />

The voltage transformer is intended to provide the secondary circuit<br />

with a secondary voltage that is proportional to that applied to the<br />

primary circuit.<br />

N.B.: IEC standard 60 186 defines the conditions which voltage transformers must meet.<br />

It comprises a primary winding, a magnetic core, one or several<br />

secondary windings, all of which is encapsulated in an insulating resin.<br />

Characteristics<br />

The rated voltage factor (KT)<br />

The rated voltage factor is the factor by which the rated primary voltage<br />

has to be multiplied in order to determine the maximum voltage for which<br />

the transformer must comply with the specified temperature rise and<br />

accuracy recommendations. According to the network's earthing<br />

arrangement, the voltage transformer must be able to withstand this<br />

maximum voltage for the time that is required to eliminate the fault.<br />

Normal values of the rated voltage factor<br />

Rated voltage Rated Primary winding connection mode<br />

factor duration and network earthing arrangement<br />

1.2 continuous phase to phase on any network<br />

neutral point to earth for star connected<br />

transformers in any network<br />

1.2 continuous phase to earth in an earthed<br />

neutral network<br />

1.5 30 s<br />

1.2 continuous phase to earth in a network<br />

without an earthed neutral with<br />

1.9 30 s automatic elimination of earthing faults<br />

1.2 continuous phase to earth in an isolated neutral network<br />

without automatic elimination of earthing faults,<br />

1.9 8 h or in a compensated network with an extinction coil<br />

without automatic elimination of the earthing fault<br />

N.B.: lower rated durations are possible when agreed to by the manufacturer and the user.<br />

Generally, voltage transformer manufacturers comply with the following<br />

values: VT phase/earth 1.9 for 8 h and VT phase/phase 1.2 continuous.<br />

Rated primary voltage (Upr)<br />

c According to their <strong>design</strong>, voltage transformers will be connected:<br />

v either phase to earth<br />

v or phase to phase<br />

3000 V<br />

e<br />

/<br />

100 V<br />

e<br />

Upr =<br />

U<br />

e<br />

3000 V / 100 V<br />

Upr = U<br />

<strong>Schneider</strong> <strong>Electric</strong><br />

Merlin Gerin <strong>MV</strong> <strong>design</strong> <strong>guide</strong><br />

61