Switchgear<br />

definition<br />

Voltage transformer<br />

Transformation ratio (Kn)<br />

Upr<br />

Kn = = for a TT<br />

Usr<br />

N1<br />

N2<br />

Voltage ratio error<br />

This is the error that the transformer introduces into the voltage<br />

measurement.<br />

voltage error (%) =<br />

(kn Usr - Upr)•100<br />

Upr<br />

Kn = transformation ratio<br />

Phase error or phase-shift error<br />

This is the phase difference between the primary voltage Upr and the<br />

secondary voltage Usr. IT is expressed in minutes of angle.<br />

The thermal power limit or rated continuous power<br />

This is the apparent power that the transformer can supply in steady state<br />

at its rated secondary voltage without exceeding the temperature rise<br />

limits set by the standards.<br />

<strong>Schneider</strong> <strong>Electric</strong><br />

Merlin Gerin <strong>MV</strong> <strong>design</strong> <strong>guide</strong><br />

63