plc pid - 25.4<br />

to a process, <strong>and</strong> tune it through trial <strong>and</strong> error. This is suitable for simpler systems, but<br />

these systems are less efficient <strong>and</strong> prone to instability. In other words it is quick <strong>and</strong> easy,<br />

but these systems can go out-of-control.<br />

25.2 CONTROL OF LOGICAL ACTUATOR SYSTEMS<br />

Many continuous systems will be controlled with logical actuators. Common<br />

examples include building HVAC (Heating, Ventilation <strong>and</strong> Air Conditioning) systems.<br />

The system setpoint is entered on a thermostat. The controller will then attempt to keep<br />

the temperature within a few degrees as shown in Figure 25.3. If the temperature is below<br />

the bottom limit the heater is turned on. When it passes the upper limit it is turned off, <strong>and</strong><br />

it will stay off until if passes the lower limit. If the gap between the upper <strong>and</strong> lower the<br />

boundaries is larger, the heater will turn on less often, but be on for longer, <strong>and</strong> the temperature<br />

will vary more. This technique is not exact, <strong>and</strong> time lags will often lead to overshoot<br />

above <strong>and</strong> below the temperature limits.<br />

upper<br />

temp.<br />

limit<br />

set temp.<br />

(nominal)<br />

lower<br />

temp.<br />

limit<br />

room<br />

temp.<br />

overshoot<br />

time<br />

heater on heater off heater on heater off heater on<br />

Note: This system turns on/off continuously. This behavior is known hunting. If the limits<br />

are set too close to the nominal value, the system will hunt at a faster rate. Therefore, to<br />

prevent wear <strong>and</strong> improve efficiency we normally try to set the limits as far away from<br />

nominal as possible.<br />

Figure 25.3<br />

Continuous <strong>Control</strong> with a Logical Actuator<br />

Figure 25.4 shows a controller that will keep the temperature between 72 <strong>and</strong> 74