Communication information<br />

No.<br />

1<br />

2<br />

3<br />

T<br />

4<br />

5<br />

6<br />

Analogue Comparator 1 Level High<br />

[612]<br />

Selects the analogue comparator constant high level<br />

according to the selected value in menu [611].<br />

The default value is 300.<br />

Default:<br />

Range:<br />

Description<br />

The reference signal passes the Level LO value from<br />

below (positive edge), the comparator CA1 output stays<br />

low, mode=RUN.<br />

The reference signal passes the Level HI value from<br />

below (positive edge), the comparator CA1 output is set<br />

high, mode=RUN.<br />

The reference signal passes the threshold level of 4 mA,<br />

the motor speed will now follow the reference signal.<br />

During this period the motor speed will follow the reference<br />

signal.<br />

The reference signal reaches the threshold level, motor<br />

speed is 0 rpm, mode = RUN.<br />

The reference signal passes the Level HI value from<br />

above (negative edge), the comparator CA1 output stays<br />

high, mode =RUN.<br />

The reference signal passes the Level LO value from<br />

above (negative edge), the comparator CA1 output=STOP.<br />

612 CA1 Level HI<br />

Stp A 300rpm<br />

300 rpm<br />

Enter a value for the high level.<br />

Modbus Instance no/DeviceNet no: 43402<br />

Profibus slot/index 170/51<br />

Fieldbus format<br />

Modbus format<br />

Long,<br />

1=1 W, 0.1 A, 0.1 V,<br />

0.1 Hz, 0.1C, 1 kWh,<br />

1H, 1%, 1 rpm or 0.001<br />

via process value<br />

EInt<br />

Example<br />

This example describes the normal use of the constant<br />

level high and low.<br />

Menu Function Setting<br />

343 Max Speed 1500<br />

611 CA1 Value Speed<br />

612 CA1 Level HI 300 rpm<br />

613 CA1 Level LO 200 rpm<br />

561 VC1 Dest Timer 1<br />

562 VC1 Source CA1<br />

MAX<br />

speed<br />

[343]<br />

300<br />

200<br />

CA1 Level HI [612]<br />

Hysteresis<br />

CA1 Level LO [613]<br />

Mode Min Max Decimals<br />

Process 0 3<br />

Speed, rpm 0 Max speed 0<br />

Torque, % 0 Max torque 0<br />

Shaft Power, kW 0 Motor P n x4 0<br />

El Power, kW 0 Motor P n x4 0<br />

Current, A 0 Motor I n x4 1<br />

Output volt, V 0 1000 1<br />

Frequency, Hz 0 400 1<br />

DC voltage, V 0 1250 1<br />

Heatsink temp, C 0 100 1<br />

PT 100_1_2_3, C -100 300 1<br />

Energy, kWh 0 1000000 0<br />

Run time, h 0 65535 0<br />

Mains time, h 0 65535 0<br />

AnIn 1-4% 0 100 0<br />

Output<br />

CA1<br />

High<br />

Low<br />

Fig. 88<br />

No.<br />

1<br />

2<br />

1 2 3 4 5 6 7 8<br />

Description<br />

The reference signal passes the Level LO value from<br />

below (positive edge), the comparator CA1 does not<br />

change, output stays low.<br />

The reference signal passes the Level HI value from<br />

below (positive edge), the comparator CA1 output is<br />

set high.<br />

t<br />

132 Functional Description <strong>Omron</strong> <strong>SX</strong> <strong>inverter</strong> <strong>manual</strong>