Condensation<br />

If the variable speed drive is moved from a cold (storage) room to a room where it will be<br />

installed, condensation can occur. This can result in sensitive components becoming damp.<br />

Do not connect the mains voltage until all visible dampness has evaporated.<br />

Grounding the <strong>inverter</strong><br />

Be sure to ground the unit. Not doing so may result in a serious injury due to an electric<br />

shock or fire.<br />

Power factor capacitors for improving cos<br />

Remove all capacitors from the motor and the motor outlet.<br />

Incorrect connection<br />

The variable speed drive is not protected against incorrect connection of the mains voltage,<br />

and in particular against connection of the mains voltage to the motor outlets U, V and W.<br />

The variable speed drive can be damaged in this way.<br />

Stop motion mechanical device to ensure safety<br />

The <strong>inverter</strong> controls the motor electrically, but has no means to stop it mechanically under<br />

some types of failures... In applications where mechanical stop is required to a degree of<br />

safety, a safety assurance study should be carried out to determine the need of additional<br />

mechanical braking devices.<br />

Braking resistor and regenerative braking units<br />

In case the application needs it, be sure to use a specified type of braking resistor/regenerative<br />

braking unit. In case of a braking resistor, install a thermal relay that monitors the temperature<br />

of the resistor. Not doing so might result in a burn due to the heat generated in the<br />

braking resistor/regenerative braking unit. Configure a sequence that enables the Inverter<br />

power to turn off when unusual overheating is detected in the braking resistor/regenerative<br />

braking unit.<br />

Electric protection of installation<br />

Take safety precautions such as setting up a molded-case circuit breaker (MCCB) or fuses<br />

that matches the Inverter capacity on the power supply side. Not doing so might result in<br />

damage to property due to the short circuit of the load.<br />

Wiring works and servicing the <strong>inverter</strong><br />

Wiring work must be carried out only by qualified personnel. Not doing so may result in a<br />

serious injury due to an electric shock. Do not dismantle, repair or modify this product if<br />

you’re not authorised and qualified for it. Doing so may result in an injury.<br />

DC-link residual voltage<br />

After switching off the mains supply, dangerous voltage can still be present in the VSD.<br />

When opening the VSD for installing and/or commissioning activities wait at least 10 minutes.<br />

In case of malfunction a qualified technician should check the DC-link or wait for one<br />

hour before dismantling the VSD for repair.<br />

Opening the variable speed drive cover<br />

Only qualified technician can open the <strong>inverter</strong>. Always take adequate precautions before<br />

opening the <strong>inverter</strong>. Although the connections for the control signals and the switches are<br />

isolated from the main voltage, do not touch the control board when the variable speed drive<br />

is switched on.<br />

Do not manipulate <strong>inverter</strong> under power<br />

Do not change wiring , put on or take off optional devices or replace cooling fans while the<br />

input power is being supplied. Doing so may result in a serious injury due to an electric<br />

shock. Inspection of the Inverter must be conducted after the power supply has been<br />

turned off. Not doing so may result in a serious injury due to an electric shock. The main<br />

power supply is not necessarily shut off even if the emergency shutoff function is activated.<br />