Table 5<br />

Flow rates cooling fans<br />

Cable dimensions 27-66 mm<br />

Frame <strong>SX</strong>-V Model Flow rate [m 3 /hour]<br />

K 4630 - 4800<br />

4800<br />

K69 6710 - 61K0<br />

10<br />

22.50<br />

Ø16(3x)<br />

300<br />

150<br />

Ø9(x6)<br />

30<br />

344,5<br />

335<br />

NOTE: For the models 4450-4500 and 6800-61K0 the<br />

mentioned amount of air flow should be divided equally<br />

over the two cabinets.<br />

2.3.2 Mounting schemes<br />

925<br />

952,50<br />

922,50<br />

2330<br />

314<br />

Fig. 9<br />

<strong>SX</strong>-V (400V): Model 4110 to 4132 (F)<br />

<strong>SX</strong>-V (690V): Model 6090 to 6160 (F69) including<br />

cable interface for mains, motor and communication<br />

2.3 Cabinet mounting<br />

2.3.1 Cooling<br />

If the variable speed drive is installed in a cabinet, the<br />

rate of airflow supplied by the cooling fans must be taken<br />

into consideration.<br />

Table 5<br />

Flow rates cooling fans<br />

600<br />

Fig. 10 <strong>SX</strong>-V (400V): Model 4160 to 4250 (G and H)<br />

<strong>SX</strong>-V (690V): Model 6200 to 6355 (H69)<br />

600<br />

Frame <strong>SX</strong>-V Model Flow rate [m 3 /hour]<br />

E 4090 510<br />

F 4110 - 4132<br />

800<br />

F69 6090 - 6160<br />

G 4160 - 4200 1020<br />

H 4220 - 4250<br />

1600<br />

H69 6200 - 6355<br />

I 4315 - 4400<br />

2400<br />

I69 6450 - 6500<br />

J 4450 - 4500<br />

3200<br />

J69 6600 - 6630<br />

14 Mounting <strong>Omron</strong> <strong>SX</strong> <strong>inverter</strong> <strong>manual</strong>