Default settings of the Run/Stop/<br />

Enable/Reset functions<br />

The default settings are shown in Fig. 28. In this example<br />

the VSD is started and stopped with DigIn 2 and a<br />

reset after trip can be given with DigIn 8.<br />

STOP<br />

(STOP=DECEL)<br />

OUTPUT<br />

SPEED<br />

t<br />

RunR<br />

Reset<br />

+24 V<br />

X1<br />

1<br />

2<br />

3<br />

4<br />

5<br />

6<br />

7<br />

8<br />

9<br />

10<br />

11<br />

12<br />

13<br />

14<br />

15<br />

16<br />

17<br />

18<br />

19<br />

20<br />

21<br />

22<br />

ENABLE<br />

OUTPUT<br />

SPEED<br />

t<br />

(06-F104_NG)<br />

(or if Spinstart is selected)<br />

Fig. 28 Default setting Run/Reset commands<br />

The inputs are default set for level-control. The rotation<br />

is determined by the setting of the digital inputs.<br />

Enable and Stop functions<br />

Both functions can be used separately or simultaneously.<br />

The choice of which function is to be used<br />

depends on the application and the control mode of<br />

the inputs (Level/Edge [21A]).<br />

NOTE: In Edge mode, at least one digital input must be<br />

programmed to “stop”, because the Run commands are<br />

otherwise only able to start the VSD.<br />

Enable<br />

Input must be active (HI) to allow any Run signal. If the<br />

input is made LOW, the output of the VSD is immediately<br />

disabled and the motor will coast.<br />

!<br />

CAUTION: If the Enable function is not<br />

programmed to a digital input, it is considered<br />

to be active internally.<br />

Stop<br />

If the input is low then the VSD will stop according to<br />

the selected stop mode set in menu [33B] Stop Mode.<br />

Fig. 29 shows the function of the Enable and the Stop<br />

input and the Stop Mode=Decel [33B].<br />

To run the input must be high.<br />

NOTE: Stop Mode=Coast [33B] will give the same<br />

behaviour as the Enable input.<br />

X<br />

Fig. 29 Functionality of the Stop and Enable input<br />

Reset and Autoreset operation<br />

If the VSD is in Stop Mode due to a trip condition, the<br />

VSD can be remotely reset by a pulse (“low” to “high”<br />

transition) on the Reset input, default on DigIn 8.<br />

Depending on the selected control method, a restart<br />

takes place as follows:<br />

Level-control<br />

If the Run inputs remain in their position the VSD will<br />

start immediately after the Reset command is given.<br />

Edge-control<br />

After the Reset command is given a new Run command<br />

must be applied to start the VSD again.<br />

Autoreset is enabled if the Reset input is continuously<br />

active. The Autoreset functions are programmed in<br />

menu Autoreset [250].<br />

NOTE: If the control commands are programmed for<br />

Keyboard control or Com, Autoreset is not possible.<br />

Run Inputs Level-controlled.<br />

The inputs are set as default for level-control. This<br />

means that an input is activated by making the input<br />

continuously “High”. This method is commonly used if,<br />

for example, PLCs are used to operate the VSD.<br />

!<br />

CAUTION: Level-controlled inputs DO NOT<br />

comply with the Machine Directive, if the inputs<br />

are directly used to start and stop the machine.<br />

The examples given in this and the following paragraphs<br />

follow the input selection shown in Fig. 30.<br />