from one VSD and then move the control panel to<br />

another VSD and download the settings.<br />

NOTE: Load from and copy to the VSD is only possible<br />

when the VSD is in stop mode.<br />

VSD<br />

The max and min alarm can be set for a trip condition.<br />

The pre-alarms act as a warning condition. All the<br />

alarms can be monitored on the digital or relay outputs.<br />

The autoset function automatically sets the 4 alarm<br />

levels whilst running: maximum alarm, maximum prealarm,<br />

minimum alarm and minimum pre-alarm.<br />

Fig. 34 gives an example of the monitor functions for<br />

constant torque applications.<br />

Fig. 33 Copy and load parameters between VSD and control<br />

panel<br />

7.5 Load Monitor and Process<br />

Protection [400]<br />

7.5.1 Load Monitor [410]<br />

The monitor functions enable the VSD to be used as a<br />

load monitor. Load monitors are used to protect<br />

machines and processes against mechanical overload<br />

and underload, such as a conveyer belt or screw conveyer<br />

jamming, belt failure on a fan or a pump dry running.<br />

The load is measured in the VSD by the<br />

calculated motor shaft torque. There is an overload<br />

alarm (Max Alarm and Max Pre-Alarm) and an underload<br />

alarm (Min Alarm and Min Pre-Alarm).<br />

The Basic Monitor type uses fixed levels for overload<br />

and underload (pre-)alarms over the whole speed<br />

range. This function can be used in constant load<br />

applications where the torque is not dependent on the<br />

speed, e.g. conveyor belt, displacement pump, screw<br />

pump, etc.<br />

For applications with a torque that is dependent on the<br />

speed, the Load Curve monitor type is preferred. By<br />

measuring the actual load curve of the process, characteristically<br />

over the range of minimum speed to<br />

maximum speed, an accurate protection at any speed<br />

can be established.<br />

40 Main Features <strong>Omron</strong> <strong>SX</strong> <strong>inverter</strong> <strong>manual</strong>