3.3.5 Output configuration<br />

The functionality associated to each of the outputs is defined during the<br />

configuration of the instrument, index L (see section 4.1).<br />

The suggested combinations are:<br />

<strong>SX25</strong> mA<br />

Output<br />

Alarms<br />

Primary Secondary AL2 AL3<br />

A Single Action Heat or Cool OP4 none none OP2 OP3<br />

B Single Action Heat or Cool OP4 none none OP1 OP3<br />

C Double Action Heat OP4 Cool OP3 OP2 -<br />

D Double Action Heat OP4 Cool OP2 - OP3<br />

E Double Action Heat OP1 Cool OP4 OP2 OP3<br />

F Double Action Heat OP2 Cool OP4 OP1 OP3<br />

OP2 output can be Relay or logic.<br />

The 'jumper' on the auxiliary<br />

board selects the output type:<br />

Link Pins 1-2 for OP2-Relay<br />

(Factory set)<br />

Link Pins 2-3 for OP2-Logic<br />

Jumper<br />

Auxiliary<br />

board<br />

<strong>SX25</strong> VMD<br />

G Valve Motor Drive Open OP1 Close OP3 OP2 OP2<br />

H Single Action Heat or Cool OP1 none none OP2 OP3<br />

I Single Action Heat or Cool OP2 none none OP1 OP3<br />

J Double Action Heat OP1 Cool OP3 OP2 -<br />

K Double Action Heat OP1 Cool OP2 - OP3<br />

L Double Action Heat OP2 Cool OP3 OP1 -<br />

OP1 - OP3<br />

OP2 - L<br />

OP2 - R<br />

Relay output<br />

Logic output<br />

Relay output<br />

Note: With heat or cool control AL2 and AL3 share the same output.<br />

14<br />