Configuration code<br />

Using the and keys, enter<br />

the first part of the configuration<br />

code 'ILMN', conf.<br />

I L M N<br />

8 0 0 2<br />

Then press the enter key<br />

Enter the last digit for code 'O'<br />

CON2.<br />

O<br />

4<br />

This selects engineering units for the input signal. Using the table below<br />

enter the following values into these parameters.<br />

Parameter Description Default Value New Value<br />

Unit Input Eng. units C bar<br />

Sc.d.d Number of decimals 0 1<br />

Sc.Lo Low input value -999.9 0.0<br />

Sc.Hi High input value 999 50.0<br />

rert Analogue output range 4 - 20 mA 4 - 20 mA<br />

rtH Output Heating/ Cooling nu nu<br />

Code Change Security code 33 33<br />

Press the enter key<br />

or press the scroll key<br />

to review the data you have entered<br />

to exit the configuration menu.<br />

Then press the enter key<br />

The configuration code is now<br />

entered, and the display will show:<br />

o C<br />

vn¡t<br />

40<br />

IM-P323-25 CH Issue 3