SX25 Series Process Controller - Spirax Sarco
SX25 Series Process Controller - Spirax Sarco
SX25 Series Process Controller - Spirax Sarco
Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
Configuration code<br />
Using the and keys, enter<br />
the first part of the configuration<br />
code 'ILMN', conf.<br />
I L M N<br />
8 0 0 2<br />
Then press the enter key<br />
Enter the last digit for code 'O'<br />
CON2.<br />
O<br />
4<br />
This selects engineering units for the input signal. Using the table below<br />
enter the following values into these parameters.<br />
Parameter Description Default Value New Value<br />
Unit Input Eng. units C bar<br />
Sc.d.d Number of decimals 0 1<br />
Sc.Lo Low input value -999.9 0.0<br />
Sc.Hi High input value 999 50.0<br />
rert Analogue output range 4 - 20 mA 4 - 20 mA<br />
rtH Output Heating/ Cooling nu nu<br />
Code Change Security code 33 33<br />
Press the enter key<br />
or press the scroll key<br />
to review the data you have entered<br />
to exit the configuration menu.<br />
Then press the enter key<br />
The configuration code is now<br />
entered, and the display will show:<br />
o C<br />
vn¡t<br />
40<br />
IM-P323-25 CH Issue 3