The AlarmPrintOff and AlarmPrintOn commands are not retained<br />

across <strong>RSView</strong> sessions. If you issue the AlarmPrintOff command<br />

before AlarmOn, alarms will not print to the printer. But if you shut<br />

down <strong>RSView</strong>, restart it, and then issue the AlarmOn command,<br />

alarms will be logged to alarm log file and the printer until you issue the<br />

AlarmPrintOff command.<br />

Suppressing alarm logging<br />

You can suppress alarm monitoring for tags. This is useful for testing<br />

or performing repairs or maintenance on equipment.<br />

To suppress alarm monitoring for tags, use the SuppressOn command.<br />

To suppress all alarms for the specified tags, issue the SuppressOn<br />

command before the AlarmOn command.<br />

For more information about <strong>RSView</strong> commands, see Help.<br />

Using the Suppressed List<br />

Use the Suppressed List to see which tags are not being monitored for<br />

alarms and to turn alarm monitoring back on.<br />

To turn off suppression<br />

for a tag, click the tag<br />

name, and then click<br />

Suppress Off.<br />

Click All Off to turn off<br />

suppression for all tags.<br />

11–34 <strong>RSView</strong> <strong>Supervisory</strong> <strong>Edition</strong> User’s <strong>Guide</strong>