Planning Guide<br />

Energy-Saving <strong>Pumps</strong><br />

Wilo-Star-E, Wilo-TOP-E, TOP-ED<br />

Wilo-TOP-E/-ED Series<br />

The world’s first electronically controlled circulating pump with<br />

standard integrated display screen and manual control panel (single<br />

button operation). It comes as standard with the unique, patented<br />

“Autopilot” automatic setback control facility based on the latest<br />

cutting-edge Fuzzy technology.<br />

Without the need for external switchgears, automatic stepless differential-pressure<br />

control offers:<br />

- Energy savings of up to 50 % and thus reduced operating costs and<br />

reduced CO 2 emissions<br />

- Elimination of noises from thermostatic valves.<br />

The Wilo-TOP-E Series covers the entire performance range from<br />

Rp 1 to DN 100 and is suitable for a fluid temperature of up to<br />

T max =110°C.<br />

Manual operation<br />

The manual operating panel serves to parameterise the basic functions<br />

of Wilo-TOP-E/-ED pumps:<br />

- On/Off control<br />

- Control mode (p-c, p-v, manual control mode)<br />

- Differential pressure setpoint<br />

- Automatic setback to minimum speed<br />

- Twin-head pump function (main/standby or parallel operation)<br />

All operating states as well as a wide range of fault and alarm signals<br />

(fault signals result in immediate shutdown) are indicated directly in<br />

the standard series pump display.<br />

auto<br />

H<br />

m<br />

on<br />

Control operation<br />

Stepless differential pressure control according to the pre-set setpoint<br />

value. Combined operating and display panel directly on the<br />

terminal box for:<br />

- selection of different control modes<br />

- setpoint adjustment in m (the lower setpoint value is 1 m)<br />

- indication of the actual operating condition on a graphical display<br />

- logging of fault and alarm signals.<br />

Control mode p-c<br />

In the p-c control mode, the electronics circuitry maintains the differential<br />

pressure generated by the pump constant at the setpoint<br />

value Hs over the permitted flow-rate range.<br />

Fig.:<br />

H<br />

H max<br />

Hs<br />

H min<br />

Control mode p-c<br />

Control mode p-v<br />

In the p-v control mode, the electronic circuitry varies the differential<br />

pressure to be maintained by the pump on a linear basis between<br />

Hs and 1 2 s. The setpoint differential-pressure value H varies with the<br />

flow volume Q.<br />

H<br />

Q<br />

Fig.:<br />

Manual operation level (pump display and operating button)<br />

H max<br />

Pump under auto control<br />

Pump at min. speed<br />

Current set point level<br />

Parallel operation<br />

Hs<br />

Automatic setback operation<br />

Keyboard lock<br />

GLT communication<br />

Control mode Dp-c<br />

Control mode Dp-v<br />

Control mode (n-const.)<br />

auto + /<br />

H<br />

RPM<br />

m x100<br />

10V on off<br />

Pump Off<br />

Pump On<br />

Standby operation<br />

Unit, motor speed<br />

Unit, delivery head<br />

Fig.:<br />

½Hs<br />

H min<br />

Control mode p-v<br />

Q<br />

Control mode Dp-T Analog input 0-10 V<br />

Fig.:<br />

Symbols featured in pump display<br />

Control technology<br />

The single and three-phase motors of the Wilo-TOP-S Series serve as<br />

the basis for the Wilo-TOP-E Series, the latter utilising the optimised<br />

hydraulics and motor design of the Wilo-TOP-S Series.<br />

32 Subject to change without prior notice 09/2006 WILO AG