Pump Management Systems Wilo-Control<br />

Pump Control<br />

Wilo-IF-Module for Single-Head <strong>Pumps</strong><br />

1 x Wilo-IF-Modul LON<br />

Plug-in module for LON-compatible single-head pumps of the series<br />

Wilo-TOP-E and Wilo-VeroLine-IP-E/CronoLine-IL-E with infrared<br />

interface<br />

Terminal diagram<br />

Wilo-IF modul LON*<br />

DP<br />

LON<br />

* The picture does not show<br />

the actual position of the terminals<br />

L N PE SSM<br />

1~230 V<br />

In<br />

0...10V<br />

+24V<br />

Wilo-TOP-E<br />

LONWORKS network<br />

Ext.off<br />

P1 500 W (P2 350 W)<br />

>Additional functions<br />

• Serial digital LON interface for connection to LONWORKS networks.<br />

Transfer of the following data items as control commands to the<br />

pump:<br />

- Operating mode<br />

-Setpoint<br />

- Data from external sensors<br />

• Transfer of the following data items as signals from the pump:<br />

-Hydraulic operating data<br />

- Electrical operating data<br />

- Status reports<br />

- Fault signals<br />

• DP twin-head pump interface for integrated dual pump management<br />

of 2 x single- or 1 x twin-head pump (see Wilo-IF-Moduls for<br />

twin-head pumps)<br />

>Standards<br />

• LONMark Application Layer Interoperability Guidelines Version 3.2<br />

• LONMark Layers 1-6 Interoperability Guidelines 3.0<br />

• LONMark Functional Profile “Pump Controller Object for HVAC<br />

Applications”<br />

>Delivery status<br />

The LON IF-Modul LON is supplied as “Application unconfigured” in<br />

line with LONMark Application Layer Interoperability Guidelines.<br />

>Documentation<br />

You will find the following documentation on our homepage at<br />

www.wilo.de (- Planning, - Data Records/CAD):<br />

LONMark Functional Profile “Pump Controller Object for HVAC<br />

Applications”<br />

• Download Application over Network: *.NXE/*.APB<br />

• External Interface Files:<br />

*.XIF/*.XFB<br />

• Device Resource Files: *.ENU/*.FMT/*.FPT/<br />

*.TYP<br />

Wilo-IF modul LON*<br />

Wilo-IP-E/IL-E<br />

DP<br />

LON<br />

3 +24 V<br />

2<br />

1 0...10 V<br />

PE<br />

L1 L2 L3<br />

3~400 V<br />

SBM<br />

SSM<br />

0/4...20mA<br />

Aux,<br />

no function<br />

Ext.off<br />

* The picture does not show<br />

the actual position of the terminals<br />

LONWORKS network<br />

450 Subject to change without prior notice 09/2006 WILO AG