Planning Guide<br />

Energy-Saving <strong>Pumps</strong><br />

Wilo-Star-E, Wilo-TOP-E, TOP-ED<br />

Control mode p-T<br />

In the p-T control mode (programmable only with the IR-Monitor)<br />

the electronics circuitry varies the setpoint differential pressure value<br />

to be maintained by the pump as a function of the measured fluid<br />

temperature. This control mode can be applied in conjunction with<br />

constant-volume (e.g. one-pipe) systems and variable-flow systems<br />

with modulating feed temperature control. Conversely, the p-T<br />

control mode supports condensing-boiler technology, provided the<br />

pump is installed in the return pipe of the system.<br />

Manual control mode<br />

RPM<br />

x100<br />

on<br />

Heating, Air-conditioning,<br />

Cooling<br />

Feed temperature [°C]<br />

Fig.:<br />

Control mode p-T<br />

“Autopilot” automatic setback mode<br />

130<br />

120<br />

100<br />

80<br />

60<br />

40<br />

20<br />

Fig.:<br />

Hs<br />

Hs max<br />

Hs min<br />

T min T max<br />

T<br />

Q min Q max<br />

Med<br />

Power consumption<br />

Feed temperature<br />

Measurement of an electronic pump with automatic setback mode<br />

The patented setback feature, by means of fuzzy control, further<br />

optimises the power input requirements of the pump during periods<br />

of low-load demand for heating systems. During periods where there<br />

is no pump performance (e.g. reduction of feed temperature by<br />

weather-/time-prompted heating controller) the pump performance<br />

is set back to a reduced constant speed.<br />

This operating mode offers further savings of up to 25 % compared<br />

with previous stepless heating circulating pumps.<br />

Hs<br />

Hs var .<br />

0<br />

0<br />

12:00 18:00 0:00 6:00 12:00 18:00 0:00 6:00 12:00 18:00<br />

Time<br />

Q<br />

65<br />

60<br />

50<br />

40<br />

30<br />

20<br />

10<br />

Power consumption [%]<br />

The manual control mode deactivates the control in the electronics<br />

module. The pump speed can be manually set to a constant value<br />

between 800 and 2,800 1/min.<br />

BA linkup<br />

Wilo-TOP-E/-ED pumps have standard series and optional interfaces<br />

for connection to external monitoring units (e.g. DDC/BA).<br />

Collective fault signal SSM<br />

All Wilo-TOP-E/-ED Series pumps are equipped with a potential-free<br />

contact (NC contact in accordance with VDI 3814) for collective fault<br />

signalling. Contact rating<br />

- min. permissible: 12 V DC, 10 mA,<br />

- max. permissible: 250 V AC, 1 A.<br />

Any fault, due to any one of the following causes, will be signalled by<br />

the collective fault signal:<br />

- motor overtemperature<br />

- module overtemperature<br />

- excess current draw<br />

- blocking<br />

- short circuit and fault to ground<br />

A power failure or a total electronics breakdown will not be assessed<br />

as such, the pump will restart automatically following restoration of<br />

power.<br />

Control input Overriding Off<br />

To enable deactivation by external control units, Wilo-TOP-E/-ED<br />

pumps are equipped with an “Ext. Aus” control input, starting with<br />

a rated motor output of P 2 = 350 W. The control input received here<br />

overrides all other control commands (contacts open: pump off).<br />

Wilo-TOP-E/-ED pumps with lower rated outputs can be switched<br />

off directly via the mains power cable.<br />

Analogue input 0 - 10 V<br />

Potable water circulation<br />

Solar thermal<br />

Service/Accessories, Systems<br />

RPM<br />

x100<br />

10V on<br />

Switchgears and Control<br />

Devices Pump Management<br />

Systems<br />

Wilo Catalogue A1 - Circulating pumps in glandless design<br />

33

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!