Pump Management Systems Wilo-Control<br />

Pump Control<br />

Wilo-IF-Module Stratos for Twin-Head <strong>Pumps</strong><br />

2 x Wilo-IF-Modul Stratos PLR<br />

Plug-in Modules for twin-head pumps of the series Wilo-Stratos-D/<br />

Stratos-ZD and Wilo-Stratos/Stratos-Z (2 pcs.).<br />

Terminal diagram<br />

Wilo-Stratos-D<br />

Wilo-Stratos<br />

Wilo-Stratos-Z<br />

Connecting cable, min. 2 x 0,75 mm 2 , lock-protected<br />

Wilo-Stratos-D<br />

Wilo-Stratos<br />

Wilo-Stratos-Z<br />

>Additional functions<br />

• Serial digital PLR interface for connection to BA building automation<br />

via<br />

- Wilo interface converters or<br />

- company-specific coupling modules<br />

• Transfer of the following data items as control commands to the<br />

pump:<br />

- Control mode<br />

- Setpoint Delivery head/Speed<br />

-Pump ON/OFF<br />

-setback mode<br />

• Transfer of the following data items as signals from the pump:<br />

- Actual value, delivery head<br />

- Actual value volumetric flow<br />

- Actual value, power consumption<br />

- Actual value, power output<br />

- Actual value, motor current<br />

- Operating hours<br />

- Actual value, speed<br />

- Detailed fault reports<br />

- Status reports<br />

• Twin-head pump interface DP for possible integration of twin-head<br />

pump management of 1 x twin-head or 2 x single-head pumps,<br />

optionally with the following functions:<br />

- Main/standby operation for automatic fault-actuated switchover to<br />

the standby pump and automatic pump duty cycling after 24 hrs.<br />

running time<br />

- Addition operation for efficiency-optimised On/Off control of the<br />

peak-load pump and automatic fault-actuated switchover to the<br />

standby pump<br />

DP<br />

PLR<br />

L N PE SSM<br />

1~230 V<br />

DP<br />

PLR<br />

L N PE SSM<br />

1~230 V<br />

(Included in the scope of delivery of the IF-Modul Stratos PLR: 2-core<br />

connecting cable, 670 mm long, a longer connecting cable to be provided<br />

by customer: Min. 2 x 0.75 mm 2 )<br />

Wilo-IF module<br />

Stratos PLR<br />

Master<br />

Wilo Interface Converter or<br />

company-specific coupling module<br />

Wilo-IF module<br />

Stratos PLR<br />

Slave<br />