Pump Management Systems Wilo-Control<br />

Pump Control<br />

Wilo-IF-Module Stratos for Twin-Head <strong>Pumps</strong><br />

Wilo-IF-Modul Stratos 1 x LON and 1 x PLR<br />

Terminal diagram<br />

Wilo-Stratos-D<br />

Wilo-Stratos<br />

Wilo-Stratos-Z<br />

DP<br />

LON<br />

Wilo-IF module<br />

Stratos LON<br />

Connecting cable, min. 2 x 0,75 mm 2 , lock-protected<br />

L N PE SSM<br />

1~230 V<br />

Master<br />

LONWORKS network<br />

DP<br />

PLR<br />

Wilo-IF module<br />

Stratos PLR<br />

Wilo-Stratos-D<br />

Wilo-Stratos<br />

Wilo-Stratos-Z<br />

L N PE SSM<br />

1~230 V<br />

Slave<br />

Plug-in Modules for twin-head pumps of the series Wilo-Stratos-D/<br />

Stratos-ZD and Wilo-Stratos/Stratos-Z (2 pcs.).<br />

For twin-head pump management a PLR module is required in addition<br />

to the LON function module.<br />

The functions of the “LON” module are applicable to the entire twinhead<br />

pump.<br />

>Additional functions<br />

• Serial digital LON interface for connection to LONWORKS networks.<br />

In the LONWORKS network, data items are transmitted for the twinhead<br />

pump as a complete single unit; there is no differentiation<br />

between Master and Slave.<br />

Transfer of the following data items as control commands to the<br />

pump:<br />

-Operating mode<br />

-Setpoint<br />

- Data from external sensors<br />

• Transfer of the following data items as signals from the pump:<br />

-Hydraulic operating data<br />

- Electrical operating data<br />

- Status reports<br />

- Fault signals<br />

• Twin-head pump interface DP for possible integration of twin-head<br />

pump management of 1 x twin-head or 2 x single-head pumps,<br />

optionally with the following functions:<br />

- Main/standby operation for automatic fault-actuated switchover to<br />

the standby pump and automatic pump duty cycling after 24 hrs.<br />

running time<br />

- Addition operation for efficiency-optimised On/Off control of the<br />

peak-load pump and automatic fault-actuated switchover to the<br />

standby pump<br />

(Included in the scope of delivery of the IF-Modul Stratos PLR: 2-core<br />

connecting cable, 670 mm long, a longer connecting cable to be provided<br />

by customer: Min. 2 x 0.75 mm 2 )<br />

>Standards<br />

• LONMark Application Layer Interoperability Guidelines Version 3.2<br />

• LONMark Layers 1-6 Interoperability Guidelines 3.0<br />

• LONMark Functional Profile “Pump Controller Object for HVAC<br />

Applications”<br />

>Delivery status<br />

The LON IF-Modul LON is supplied as “Application unconfigured” in<br />

line with LONMark Application Layer Interoperability Guidelines.<br />

>Documentation<br />

You will find the following documentation on our homepage at<br />

www.wilo.com (- Planning, - Data Records/CAD):<br />

LONMark Functional Profile “Pump Controller Object for HVAC<br />

Applications”<br />

• Download Application over Network: *.NXE/*.APB<br />

• External Interface Files:<br />

*.XIF/*.XFB<br />

• Device Resource Files:<br />

*.ENU/*.FMT/*.FPT/*.TYP<br />

Heating, Air-conditioning,<br />

Cooling<br />

Potable water circulation<br />

Solar thermal<br />

Service/Accessories, Systems<br />

Switchgears and Control Devices<br />

Pump Management Systems<br />

Wilo Catalogue A1 - Circulating pumps in glandless design<br />

441