Pump Management Systems Wilo-Control<br />

Pump Control<br />

Wilo-IF-Module Stratos for Twin-Head <strong>Pumps</strong><br />

Wilo-IF-Modul Stratos 1 x Ext. Min and 1 x PLR<br />

Terminal diagram<br />

Wilo-Stratos-D<br />

Wilo-Stratos<br />

Wilo-Stratos-Z<br />

Connecting cable, min. 2 x 0,75 mm 2 , lock-protected<br />

DP<br />

0...10V<br />

Ext.<br />

Min<br />

Wilo-IF module<br />

Stratos Ext. Min<br />

L N PE SSM<br />

1~230 V<br />

Master<br />

Remote contact<br />

– Ext. potential-fre contact (Input):<br />

Closed contacts: Twin-head pump on<br />

Open contactst: Twin-head pum "off"<br />

– For remote actuation, remove bridge<br />

DP<br />

PLR<br />

Wilo-IF module<br />

Stratos PLR<br />

Wilo-Stratos-D<br />

Wilo-Stratos<br />

Wilo-Stratos-Z<br />

L N PE SSM<br />

1~230 V<br />

Slave<br />

Plug-in Modules for twin-head pumps of the series Wilo-Stratos-D/<br />

Stratos-ZD and Wilo-Stratos/Stratos-Z (2 pcs.).<br />

For twin-head pump management a PLR module is required in addition<br />

to the Ext. Min function module.<br />

The functions of the Ext. Min module are applicable to the entire<br />

twin-head pump.<br />

>Additional functions<br />

• Input for potential-free NC contact with Ext. Min function (setback<br />

mode without autopilot)<br />

- Contact closed: pump operating under auto control<br />

- Contact open: pump runs at fixed minimum speed<br />

• Control input 0 - 10 V for remote setpoint adjustment or remote<br />

speed adjustment (cable shielded)<br />

- Remote setpoint adjustment:<br />

The setpoint value for integrated differential-pressure control is<br />

determined for the pump via an analogue signal 0 - 10 V<br />

(see “High-Efficiency <strong>Pumps</strong> Planning Guide”).<br />

- Remote speed adjustment:<br />

An external controller issues an actuating signal for remote speed<br />

adjustment (DDC operation). This actuating signal acts on:<br />

- the active pump in each case in main/standby operation<br />

- Both pumps simultaneously (synchronously) in parallel operation<br />

(synchronous)<br />

(also see “High-Efficiency <strong>Pumps</strong> Planning Guide”).<br />

The desired function must be activated at the pump.<br />

• Twin-head pump interface DP for possible integration of twin-head<br />

pump management of 1x twin-head or 2x single-head pumps,<br />

optionally with the following functions:<br />

- Main/standby operation for automatic fault-actuated switchover to<br />

the standby pump and automatic pump duty cycling after 24 hrs.<br />

running time<br />

- Addition operation for efficiency-optimised On/Off control of the<br />

peak-load pump and automatic fault-actuated switchover to the<br />

standby pump<br />

(Included in the scope of delivery of the IF-Modul Stratos PLR: 2-core<br />

connecting cable, 670 mm long, a longer connecting cable to be provided<br />

by customer: Min. 2 x 0.75 mm 2 )<br />

>Delivery status<br />

The terminals of the Ext. Min control input are bridged.<br />

Heating, Air-conditioning,<br />

Cooling<br />

Potable water circulation<br />

Solar thermal<br />

Service/Accessories, Systems<br />

Switchgears and Control Devices<br />

Pump Management Systems<br />

Wilo Catalogue A1 - Circulating pumps in glandless design<br />