Figure 3-7<br />

Airflow Requirement vs. Inlet Temperature for the 31S1P at 270W TDP and<br />

SE10P/7120P/3120P at 300W TDP<br />

Card Inlet ( o C) Total Flow (ft^3/min) Primary (ft^3/min) Secondary (ft^3/min) Card dP (inH 2O)<br />

20 14.4 10.5 3.9 0.13<br />

21 14.7 10.8 3.9 0.13<br />

22 15 11.1 3.9 0.14<br />

23 15.3 11.3 3.9 0.14<br />

24 15.6 11.7 4 0.15<br />

25 16 12 4 0.15<br />

26 16.3 12.3 4 0.16<br />

27 16.7 12.7 4.1 0.16<br />

28 17.1 13 4.1 0.17<br />

29 17.6 13.4 4.1 0.18<br />

30 18 13.8 4.2 0.19<br />

31 18.5 14.3 4.3 0.2<br />

32 19.1 14.8 4.3 0.21<br />

33 19.7 15.3 4.4 0.22<br />

34 20.3 15.8 4.5 0.23<br />

35 21 16.4 4.6 0.24<br />

36 21.7 17 4.7 0.26<br />

37 22.5 17.6 4.8 0.27<br />

38 23.3 18.4 5 0.29<br />

39 24.3 19.1 5.1 0.31<br />

40 25.3 20 5.3 0.34<br />

41 26.5 20.9 5.6 0.37<br />

42 27.8 21.9 5.9 0.4<br />

43 29.2 23 6.2 0.44<br />

44 30.9 24.2 6.7 0.48<br />

45 32.8 25.6 7.2 0.54<br />

Intel ® <strong>Xeon</strong> <strong>Phi</strong> <strong>Coprocessor</strong> <strong>Datasheet</strong><br />