gENERaL<br />

1 BOILER DIMENsIONs, sERVICEs & CLEaRaNCEs all dimensions in mm<br />

The boiler connections are made on the boiler bulkhead fittings.<br />

Refer to Frame 28.<br />

The following minimum clearances must be maintained for<br />

operation and servicing.<br />

Additional space will be required for installation, depending upon<br />

site conditions.<br />

side and Rear Flue<br />

a. Provided that the flue hole is cut accurately, e.g. with a core<br />

drill, the flue can be installed from inside the building where<br />

Front clearance<br />

The minimum front clearance when built in to a cupboard is 5mm<br />

from the cupboard door but 450mm overall clearance is still<br />

required, with the cupboard door open, to allow for servicing.<br />

395<br />

* Bottom clearance<br />

Bottom clearance after installation can be reduced to 5mm.<br />

This must be obtained with an easily removable panel, to enable<br />

the consumer to view the system pressure gauge, and to provide<br />

the 100mm clearance required for servicing.<br />

REaR FLUE ONLy<br />

MIN. Top clearance required = 165 mm<br />

wall thicknesses do not exceed 600mm (<strong>24</strong>”). Where the<br />

space into which the boiler is going to be installed is less<br />

than the length of flue required the flue must be fitted from<br />

the outside.<br />

Installation from inside ONLy<br />

b. If a core boring tool is to be used inside the building the<br />

space in which the boiler is to be installed must be at least<br />

wide enough to accommodate the tool.<br />

10 i-mini - Installation and Servicing<br />

700<br />

sIDE FLUE ONLy<br />

Horizontal length of flue from Top clearance required<br />

CL of boiler to outside wall (MIN.) Dim. A<br />

<strong>24</strong> <strong>30</strong><br />

0.5 m 0.5 m 165 mm<br />

1.0 m 1.0 m 170 mm<br />

1.5 m 1.5 m 185 mm<br />

2.0 m 2.0 m 200 mm<br />

2.5 m 2.5 m 210 mm<br />

3.0 m 3.0 m 225 mm<br />

3.5 m 3.5 m 250 mm<br />

4.0 m 4.0 m 260 mm<br />

4.5 m 4.5 m 265 mm<br />

5.0 m 5.0 m 275 mm<br />

5.5 m 5.5 m 290 mm<br />

6.0 m 6.0 m <strong>30</strong>0 mm<br />

6.5 m 6.5 m 320 mm<br />

7.0 m 7.0 m 3<strong>30</strong> mm<br />

7.5 m 7.5 m 345 mm<br />

8.0 m 8.0 m 360 mm<br />

8.5m N/A 370 mm<br />

9.0 m N/A 385 mm<br />

205367-10213b