FLUE OUTLET<br />

18<br />

14 sETTINg ThE FLUE - REaR<br />

Notes.<br />

a. If using the extension ducts go to Frame 16.<br />

b. For shorter flue requirements use non telescopic B<br />

Pack.<br />

c. If the stand-off frame is used it is essential to add 45mm<br />

to ‘X’ the measured wall thickness when marking the<br />

flue (this will allow for the fitted frame).<br />

INsTaLLaTION<br />

13 TERMINaL WaLL sEaL assEMBLy / pOsITIONINg<br />

Prior to fitting the flue, the rubber terminal wall seal provided Once the flue is installed it is IMPORTANT that the rubber<br />

in the flue pack MUST be fitted to the flue terminal as shown terminal wall seal is pressed against the outside wall to create<br />

below in Figure 1.<br />

an adequate seal between the flue and wall as shown in<br />

Figure 2.<br />

FIgURE 1 FIgURE 2<br />

isfu9783<br />

Wall Seal Lip<br />

Step<br />

Ensure lip of wall seal is positioned<br />

over step on plastic nose of flue terminal<br />

(note, seal is cut away for clarity)<br />

non Telescopic Flue - Wall thickness of 115mm to 485mm<br />

Notes.<br />

a. If using the extension ducts go to Frame 16.<br />

b. If the stand-off frame is used it is essential to add 45mm<br />

to ‘X’ the measured wall thickness when marking the flue<br />

(this will allow for the fitted frame).<br />

1. Measure and note wall thickness x. Refer to Frame 8.<br />

2. Add 90mm to dimension x and, measuring from the ring,<br />

cut the outer tube only.<br />

3. To ensure the tube is cut square, mark the flue all the way<br />

around.<br />

4. Cut the inner tube to a length 20mm longer to aid<br />

engagement, using the cutting aid provided.<br />

Telescopic Flue - Wall thickness of 195mm to 420mm<br />

1. Measure and note wall thickness x. Refer to Frame 8.<br />

2. Add 75mm to dimension x and set telescopic flue length<br />

as indicated in drawing.<br />

3. Using a 3.5mm drill bit, drill one hole in outer air duct<br />

taking care not to pierce plastic inner flue.<br />

4. Fix to length using self tappers provided.<br />

5. Seal outer air duct using the tape provided. nm8944<br />

Drill hole<br />

var9784<br />

X + 75<br />

3G9675<br />

Measurement to be<br />

taken from this point<br />

Measure from<br />

this<br />

RING<br />

Adhere sealing tape<br />

Rubber<br />

Terminal<br />

Wall Seal<br />

i-mini - Installation and Servicing